3.10
Checksum calculation method
3-11
Calculation example
Example) Change circulating fluid set temperature 23.4 ° C
Sending data
0106004000EA
○
Slave Address : No.1
○
Function : No.06
○
Writing address : 0040h
○
Writing data : 00EAh
Data No.
1st value
2nd value
3rd value
4th value
5th value
6th value
Data
contents
0001h
0006h
0000h
0040h
0000h
00EAh
No
Classification
Contents
Result
1
CRC
message for
calculation
0106000B00FE
-
2
Calculation
Perform (1) to (4) for the 1st value (0001h) and then,
perform (5).
807Eh
3
Perform (6) for 2nd value (0006h) and then, perform (5).
2280h
4
Perform (6) for 3rd. value (0000h) and then, perform (5).
A023h
5
Perform (6) for 4th value (0040h) and then, perform (5).
29E0h
6
Perform (6) for 5th value (0000h) and then, perform (5).
8828Eh
7
Perform (6) for 6th value (00EAh) and then, perform (5).
9109h
(CRC)
8
Addition to the
sent message
0106004000EA0991
1
-
1
When incorporating it into the message, set it in order of low byte and high byte.