Unit parameter object (Class: 78h)
Instance Attribute Access
Name
Type
Value
64h
Short circuit detection
(Power supply for input device)
•Digital input, I/O
•Analogue input, output, I/O
BOOL
0: Disable
1: Enable
65h
Short circuit detection (Output)
•SI
•Digital output, I/O
BOOL
0: Disable
1: Enable
66h
Analogue over range detection
•Analogue input, I/O
BOOL
0: Disable
1: Enable
67h
Analogue under range detection
•Analogue input, I/O
BOOL
0: Disable
1: Enable
68h
Inrush current filter
•Digital input, I/O
BOOL
0: Disable
1: Enable
69h
Restart after output load short circuit
•SI
•Digital output, I/O
BOOL
0: Manual
1: Auto
6Ah
Input filtering time
•Digital input, I/O
USINT
0: 0.1 ms
1: 1.0 ms
2: 10 ms
3: 20 ms
6Bh
Input extension time
•Digital input, I/O
USINT
0: 1.0 ms
1: 15 ms
2: 100 ms
3: 200 ms
6Ch
Analogue data format
•Analogue input, output, I/O
USINT
0: Offset binary
1: Sign and Magnitude
2: 2’s complement
3: Scaled
(Scaled cannot be set for analogue
input)
6Dh
Power supply for control and input
voltage monitor
•SI
BOOL
0: Disable
1: Enable
01h to
0Ah
1
6Eh
Get/Set
Power supply for output voltage
monitor
•SI
BOOL
0: Disable
1: Enable
1: The instance number 01h to 0Ah is allocated to the Unit No. from 0 to 9.