-18-
EX
※※
-OMR1012
Switch setting
The range of IP address that can be set changes by 5 of the settings1.
(1) 5 of the settings1 is OFF
IP address range: 192.168.0.1 to 192.168.1.254.
Subnet mask: 255.255.255.0
Settings1
Settings2
1 Hold/Clear
setting
1
2 Diagnostics
setting
2
3 3
4
Reserved
4
5
OFF
5
6 6
7
Reserved
7
8
IP address byte 3 setting
8
•IP address byte 4 setting
•DHCP mode setting
•HOLD/CLEAR switch: Sets the output status when the fieldbus has a communication error or is in idling
state.
Settings1
1
Content
OFF
Output is OFF. (default setting)
ON
Holds the output.
: This switch can be enabled and disabled by parameter.
•Switch for diagnosis: Allocates the diagnostic data to the input data.
Settings1
2
Mode
Content
Diagnostic size set
for the input
OFF
0
Input data only (default setting)
0 byte
ON
1
Input data + System dia Unit diagnosis
4 bytes
●
Precautions for handling
•Handle the switch with care. Excessive force can break the switch.
•3, 4, 6, 7 of the Settings1 switch are not used.