-51-
EX
※※
-OMR1012
(2) Signed binary data format & 2's complement data format
•Range: 0 to 10 V, 0 to 5 V, 0 to 20 mA
•Range: 1 to 5 V, 4 to 20 mA
Settable value
by PLC
(AD value)
Output signal range
(0 to b)
Voltage
[V]
Current
[mA]
Decimal
number
0 to 10
0 to 5
0 to 20
2047 10.5
5.25
21
1950 10
5 20
1024 5.25
2.625
10.5
0 0
0
0
Settable value
by PLC
(AD value)
Output signal range
(a to b)
Voltage
[V]
Current
[mA]
Decimal
number
1 to 5
4 to 20
2047 5.25
21
1934 5
20
1024 3
12
114 1
4
0 0.75
3
Example: To set the Fault value to 10 V when signed binary data format (analogue data format) and
range 0 to 10 V (analogue output range) are set, the value set to PLC is "1950" from the table
on the left.
(3) Scaled data format
If the data format is scaled data format, set the data as follows, regardless of the range setting.
•PLC set value: 0 to 32767
→
Converted value +0 to +32767
•PLC set value: 32768 to 65535
→
Converted value -0 to -32767