-47-
EX
※※
-OMR1012
•Analogue I/O unit parameters (1)
Parameter
setting
No.
Parameter
Definition
Item
Content
Default
setting
By
E.O.
By
W.S.
Enable Generates
an
error.
○
1
The power
supply short
circuit
detection for
the input or
output device
Generates error
per unit when the
short circuit of the
input device power
supply or output
device is detected.
Disable
Does not generate an
error.
○
○
0..10 V
0..5 V
1..5 V
0..20 mA
2
Analogue
input or
output range
Sets the analogue
input or output
device range per
channel.
4..20 mA
Selects the analogue
input or output range
1..5 V
○
○
Offset binary
Offset binary.
○
Sign &
Magnitude
Signed binary.
2s complement
2’s complement.
3
Analogue
data format
Sets analogue data
type which is
output to PLC per
unit.
Scaled
Scale conversion type.
○
○
None None
2AVG
2 value average
○
4AVG
4 value average
4
Analogue
average filter
Sets analogue
filtering time per
channel.
Sampling interval is
approx. 2 sec.
8AVG
8 value average
○
○
Enable Generates
an
error.
5
Over range
detection
Generates error
per unit when the
input value
exceeds 0.5% of
full span.
Disable
Does not generate an
error.
○
○
○
Enable Generates
an
error.
6
Under range
detection
Generates error
per unit when the
input value falls
below 0.5% of full
span.
Disable
Does not generate an
error.
○
○
○
Enable Generates
an
error.
1
User’s set
value upper
limit error
Generates error
per channel when
the input or output
value exceeds the
set value.
Disable
Does not generate an
error.
○
Enable
Generates an error.
Val: -32766 to 32767
7
Scale upper
limit setting
Sets the scale
upper limit.
Generates error
per channel when
the input or output
value exceeds the
upper limit.
Disable
Does not generated an
error.
Val: -32766 to 32767
○
Val: 1000
○
○