-20-
No.EX
※※
-OME0014-F
Assignment of I/O No.
Correspondence between output data and valve manifold
: Output numbers are assigned to stations from side D to U of manifold in order. (See manual of each valve manifold for the
directions of side D and U)
: Standard manifold is wired in double. Output numbers are assigned to side A and B alternatively. In case of single solenoid valve,
output on side B is free. (Refer to fig. a)
: Mixed (single and double) wiring is available as long as wiring specifications designate it. This allows output numbers to be
specified without having free output. (Refer to fig. b)
: Each bit of data sent from master (4 bytes) shows ON/OFF (0: OFF, 1: ON) of solenoid valve. Starting from LSB of the first byte
(Offset 0), output numbers are assigned to all the bits in numeric order.
Содержание EX250-SPR1
Страница 30: ...Dimensions 29 No EX OME0014 F ...