-17-
No.EX
※※
-OME0014-F
Byte1: Station Status 2
Bit 7 0
0
X X X 0 1 0 X
Byte2: Station Status 3
Bit 7 0
0
X X X X X X X
Byte3: Diag.Master_Add
Indicates the master address.
Byte4, 5: Ident_Number
Indicates ID No. of SI unit.
Byte6: Diag.Header
Indicates how many bits the enhancing diagnosis data has. (7 byte: fixed)
Byte7: SI unit status information
Bit 7
0
0 0
0
0
0
0
0
0
Byte8 to 12: Reserved (All 00h)
Diag. Ext_Overflow
“1” when the enhancing
diagnosis data causes
overflow
Reserved
Diag. Prm_Req
“1” when the SI unit setting is
rewritten by the master
Diag. Stat_Diag
“1” when it has a diagnosis
Diag. WD_on
The watchdog is in active
state
Diag. Deactivated
“1” when SI unit is stopped
Reserved
Diag. Sync_Mode
“1” when Sync command is
received
Diag. Freeze_Mode
“1” when Freeze command is
received
If Input Block turns cut-off: “1”
Reserved
If solenoid valve power supply
voltage drops: “1”
Reserved