Chapter 5 Display and setting of various functions
HRS-R Series
5.8
Signal for completion of preparation (TEMP READY)
5-19
5.8 Signal for completion of preparation (TEMP
READY)
5.8.1
Signal for completion of preparation (TEMP READY)
This function sets the band width for the circulating fluid set temperature
(upper/lower temperature range) in order to notify the customer by
communication that the circulating fluid temperature has reached the band
range (upper/lower temperature range).The default setting of this function is
“OFF”.
【
Tips
】
This function is available when contact input/output and serial communication
is used. Refer to the Communications Operation Manual for more details.
An example is shown below.
Circulating fluid set temperature
:
20
o
C
READY band width (upper/lower
temperature range)
:
±2
o
C
READY time
:
60 sec.
Preparation is completed 60 seconds after the circulating fluid temperature
reaches 18
o
C to 22
o
C.
Circulating set fluid 20
℃
READY TEMP 22
℃
READY TEMP 18
℃
READY band width
(
upper/lower temperature range
)
2
℃
READY band width
(
upper/lower temperature range
)
2
℃
Circulating set fluid
READY time
60
sec
Completion
of preparation
READY time
lower than
60
sec
Contact output
:
State generation output
Serial
:
ON output
Contact output
:
State not generation output
Serial
:
OFF output
Completion of preparation
(
TEMP READY
)
Содержание HRS018-A 20 R Series
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10 ...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6 ...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28 ...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4 ...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10 ...
Страница 161: ......