HRX-OM-W058
Chapter 3 Transport and Setting Up
HRS-R Series
3.4
Piping
3-21
How to connect piping
Tighten the piping to
circulating fluid outlet
/
return port
.
Fig. 3-13 Tightening of piping
Recommended piping circuit
Fig. 3-14 Recommended piping circuit
No.
Description
Size
Recommended part no.
Note
1
Valve
Rc1/2
-
-
Y-strainer
Rc1/2
#500 to 1000
-
Filter
Rc1/2
20μm
HRS-PF003
3
Flow meter
0 to 50L/min
-
-
4
Pressure gauge
0 to 1.0MPa
-
-
5
Others (pipe, hose, etc.)
ø15 or more
-
-
2
Install either the strainer or filter. If foreign objects
with a size of 20 μm or more are likely to enter,
install the particle filter.
Outlet
Rc1/2
Return
Rc1/2
Sealant material
Piping port
Circulating fluid
return port
1
1
1
1
4
1
3
2
4
Circulating fluid
outlet
Thermo-chiller
User's
equipment