Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
158
2.
Check the "Correct operation
”
signal transmitted to the Fire Alarm System. In case the
signal is not forwarded by the unit, it is necessary to start service activities, based on the
device's technical documentation, aimed at diagnosing and removing failures.
6.
Check the activation of the aeration fan (frequency inverter) 15 seconds after the SAP signal
is given. In case the aeration unit is not activated, it is necessary to start service activities,
based on the device's technical documentation, aimed at diagnosing and removing failures.
7.
Check the indications of the differential pressure values between the protected space and
the reference space on the held overpressure display on the TSS panel. Where all doors to
the protected space are closed (not applicable to lift shafts), the pressure indication should
be in accordance with the design guidelines for the facility. In case of lack of stable
pressure value on the display, it is necessary to start service activities, based on the
device's technical documentation, aimed at diagnosing and removing failures. If an MSPU
is installed, the pressure values are displayed on the monitor screen in the visualization
program.
8.
Check whether the "SAP Fire" fire alarm light on the TSS panel has gone out after removing
and deactivating the SAP signal. In case the indication light goes off, it is necessary to start
service activities, based on the device's technical documentation, aimed at diagnosing and
removing failures. In case the aeration fan would not stop its operation, it is necessary to
start service activities, based on the device's technical documentation, aimed at diagnosing
and removing failures.
9.
Check the condition of the shut-off damper. Approximately one hundred and fifty seconds
after the aeration fan has been switched off, the shut-off damper goes into the fully closed
position. In case of no return to such state, it is necessary to start service activities, based
on the device's technical documentation, aimed at diagnosing and removing failures.
18.3.
Manual test of the device with control of operating parameters.
Manual testing of the device can be performed by a person who has received SMAY service
training or an authorized SMAY service provider confirmed by a "Training Protocol" for iSWAY-FC,
iSWAY-WFC, iSWAY-RFC devices (SAFETY WAY system). Manual testing of the device may only be
carried out if the device aerates a single space (staircase, lift, etc.) and there are no fire ventilation
flaps in the airway that would have to open.
In order to correctly perform all activities related to the manual test of the iSWAY-FC, iSWAY-WFC,
iSWAY-RFC with performance control, it is necessary:
1.
Change the unit's operating mode switch "Fan manual switch-on" , on a TSS or TS panel,
from "A" position - auto to "R" position - hand. After 15 seconds the aeration fan should be
switched on.
2.
Check that the equipment/system is working acceptably - according to the "Fire
Emergency Scenario" for the specific building/system.
3.
Change the "Manual fan activation" switch on the TSS panel from position "R" to position
"A". The aeration fan should stop working. In case the aeration fan would not stop its
operation, it is necessary to start service activities, based on the device's technical
documentation, aimed at diagnosing and removing failures.
4.
Leave the device in standby mode.