HGM4100LT GENSET CONTROLLER USER MANUAL
HGM4100LT Genset Controller 2019-01-28 Version1.0 Page 20 of 48
No.
Function
Cable
Size
Remarks
34
CT
C-phase
monitoring
input
1.5mm
2
Externally connected to CT secondary coil (5A
rated);
35
CT COM
1.5mm
2
Reference to
Installation Instruction
NOTE:
USB ports in controller back panel are programmable parameter ports, and users can directly
configure the controller via PC.
7
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
7.1 CONTENTS AND SCOPES OF PARAMETERS
Table 7 Contents and Scopes of Parameter Settings
No
Items
Range
Default
Description
1
Start Delay
(0-3600)s
1
From time when remote start signal is active to
the time when the genset starts;
2
Stop Delay
(0-3600)s
1
From time when remote start signal is reactive
to time when the genset stops;
3
Start Attempts
(1-10)times
3
The max. crank attempts for start failure; when
it reaches the crank times, the controller shall
send start failure signal.
4
Preheat Delay
(0-300)s
0
Power-on time of heater plug before starter is
powered up;
5
Cranking Time
(3-60)s
8
Power-on time of starter every time;
6
Crank Rest Time
(3-60)s
10
The waiting time before the second power on
when engine fails to start;
7
Safety On Delay
(1-60)s
10
During this period, low oil pressure, high
temperature, under speed, under frequency,
under voltage, charge alt failure alarms are all
inactive.
8
Start Idle Time
(0-3600)s
0
Running time at idling speed when genset
starts;
9
Warming Up Time
(0-3600)s
10
Warming up time before breaker close and after
high speed running;
10
Cooling Time
(3-3600)s
10
Radiating time before genset stop, after it
unloads.
11
Stop Idle Time
(0-3600)s
0
Idle running time when genset stop.
12
ETS Solenoid Hold (0-120)s
20
Power-on time for stop coil after genset
unloads;
13
Fail to Stop Delay
(0-120)s
5
Time from end of idling speed delay to complete
stop when ETS output time is set
“0”; Time from
end of ETS delay to complete stop when ETS
output time is not
“0”;
14
Switch Close Time
(0-10)s
5.0
Width of generator close pulse; Continuous
output when it is 0;
15
Flywheel Teeth
(10.0-300.0) 118.0
Flywheel teeth of engine; which is used for
judging starter disconnection conditions and