HGM4100LT GENSET CONTROLLER USER MANUAL
HGM4100LT Genset Controller 2019-01-28 Version1.0 Page 17 of 48
No.
Type
Description
Open
sensor port, is open circuit, and the open circuit action in
parameter configuration is selected
“shutdown”, it will send stop
alarm signals and the corresponding alarm information will be
displayed on LCD.
22
High Temp. 2
Shutdown
When the sample value adopted by the programmable sensor
(sensor type: temperature sensor), is higher than the pre-set
value, it will send stop alarm signals and the corresponding
alarm information will be displayed on LCD.
23
Low Pressure 2
Shutdown
When the sample value adopted by the programmable sensor
(sensor type: pressure sensor), is lower than the pre-set value, it
will send stop alarm signals and the corresponding alarm
information will be displayed on LCD.
24
Low Coolant Level
Shutdown
When the sample value adopted by the programmable sensor
(sensor type: liquid level sensor), is lower than the pre-set value,
it will send stop alarm signals and the corresponding alarm
information will be displayed on LCD.
25
Maintenance Due
When genset operation time exceeds the users-set maintenance
time and the maintenance action is set
“shutdown”, it will send
stop alarm signals and the corresponding alarm information will
be displayed on LCD.
26
Over Power Shutdown
Alarm
When the controller detects the power value (power is positive)
is higher than the set limit value and the over power action type
is set
“shutdown”, it will send stop alarm signals and the
corresponding alarm information will be displayed on LCD.
27
Digital Input Port Alarm
Shutdown
When the controller detects external shutdown alarm signals are
active, it will send stop alarm signals and the corresponding
alarm information will be displayed on LCD.
28
ECU Alarm Shutdown
When the controller receives the stop alarm signals by J1939, it
will send stop alarm signals.
29
ECU Fail to
Communication
When the controller does not receive data by J1939 when it
starts the engine, it will send stop alarm signals for
communication failure.
NOTE:
ECU warning and shutdown alarms illustration: if there are detailed alarms displayed, check the engine
according to the information; otherwise refer to the engine manual to obtain information according to SPN alarm code.