HGM4100LT GENSET CONTROLLER USER MANUAL
HGM4100LT Genset Controller 2019-01-28 Version1.0 Page 13 of 48
No.
Type
Description
10
Loss Of Speed
Signal
When the controller detects that the engine speed is 0 and the delay is 0,
it will initiate a warning alarm and the corresponding alarm information
will be displayed on LCD.
11 Low Coolant Level
When the controller detects the low coolant level input is active, it will
initiate a warning alarm and the corresponding alarm information will be
displayed on LCD.
12
Temp.
Sensor
Open
When the controller detects that the temperature sensor is open circuit
and the open circuit action is set as
“Warn” in parameter setting, it will
initiate a warning alarm and the corresponding alarm information will be
displayed on LCD.
13
Oil
Pressure
Sensor Open
When the controller detects that the oil pressure sensor is open circuit
and the action select “Warn”, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
14
Level
Sensor
Open
When the controller detects that the level sensor is open circuit and the
action is selected
“Warn”, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
15
Temp. Sensor 2
Open
If the temperature sensor connected with config. sensor port is open
circuit, the open circuit action configured in the parameter configuration
is set as
“Warn”, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
16
Oil
Pressure
Sensor 2 Open
If the pressure sensor connected with config. sensor port is open circuit,
the open circuit action configured in the parameter configuration is set as
“Warn”, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
17
Coolant
Level
Sensor 2 Open
If the level sensor connected with config. sensor port is open circuit,
the open circuit action configured in the parameter configuration is set as
“Warn”, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
18
High
Temperature 2
When the controller detects that config. sensor temperature (sensor
type: temperature sensor) has exceeded the pre-set value while
shutdown is prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
19 Low Oil Pressure 2
When the controller detects that config. sensor oil pressure (sensor type:
oil pressure sensor) has fallen below the pre-set value while shutdown is
prohibited, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
20 Low Coolant Level
When the controller detects that config. sensor coolant level (sensor
type: level sensor) has fallen below the pre-set value while shutdown is
prohibited, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.