Страница 3: ...th 3 working modes that can be selected from the front panel It can detect one phase generator voltage and current can be started and stopped manually or via a remote start stop signals In case of fau...
Страница 4: ...enerator frequency Hz Generator current A Engine temperature C Oil pressure kPa Engine speed rpm Total running time H Battery voltage V Fuel level Generator voltage battery voltage engine speed temper...
Страница 5: ...uts fuel relay start relay 1 configurable output port which can be set as common alarm output fail to stop output preheat output or idle control output Parameters can be set and modified by users and...
Страница 6: ...changes every six minutes Start Relay Output 1Amp DC28V DC B power supply Fuel Relay Output 1Amp DC28V DC B power supply Programmable Relay Output 1Amp DC28V DC B power supply Digital Input Active whe...
Страница 7: ...ut down the generator and place it into its standby mode in case of alarm pressing this button will clear alarms Turn Page Confirm Using this button you can scroll pages of the LCD monitor in settings...
Страница 8: ...preheat delay begins One second before it is finished fuel output will 4 3 DISPLAY DESCRIPTION Generator phase voltage Ua frequency F Loading current la engine speed Oil pressure water temperature Liq...
Страница 9: ...seconds after the beginning of the delay preheat and ETS outputs will be activated after the end of the delay ETS output will be deactivated and fuel relay output preheat output will be deactivated be...
Страница 10: ...nly react to emergency stop signal Note Configurable output ports can be set as one of the following functions ETS output Idle output or Preheat output via PC Therefore all three functions can not be...
Страница 11: ...ry voltage warning signal is sent Only warning and not shutdown 9 Low Battery Voltage if battery voltage stays below the pre set value for 20 seconds low battery voltage warning signal is sent Only wa...
Страница 12: ...il P06 Safety On Delay 1 60 s 10 Alarms for low oil pressure high temperature under speed under frequency voltage charge fail are inactive P07 Start Idle Time 0 3600 s 0 Idle running time of genset wh...
Страница 13: ...speed falls below this value and stays so for 10 seconds this is regarded as under speed and under speed alarm shutdown signal is sent P19 Engine Over Speed 0 6000 RPM 1710 When engine speed exceeds...
Страница 14: ...attery Over Volts 12 40 V 33 0 When battery voltage exceeds this value and stays so for 20 seconds Battery Over Volts signal is send and warning without shutdown is initiated P27 Battery Under Volts 4...
Страница 15: ...ossible P37 Disconnect Engine Speed 0 3000 RPM 360 When generator speed higher than the set value starter will be disconnected P38 Disconnect Generator Freq 10 30 Hz 14 0 When generator frequency high...
Страница 16: ...isconnects after complete stop 4 Preheat control It closes before starting and opens before starter is power on 5 Closing Gens During normal operation of the generator closes the breaker 6 Reserved No...
Страница 17: ...Dongkang sensor 7 CURTIS 8 DATCON 10Bar 9 VOLVO EC 10 SGX 10Bar Digital closed and Digital open both are digital signal low or high electrical level can be selected to be active connecting to earth p...
Страница 18: ...er motor as soon as possible 2 Magnetic pickup is the magnetic equipment which be installed in starter for detecting flywheel teeth 3 When set as magnetic pickup must ensure that the number of flywhee...
Страница 19: ...y that is used for password to enter the set value Password Parameter Setting Attention 1 Please change the controller parameters when generator is in standby mode only e g Crank disconnect conditions...
Страница 20: ...rk 2 If the generator is in manual mode and crank disconnect condition is set as 2 magnetic pickup generator frequency or 5 generator frequency magnetic pickup oil pressure and generator frequency and...
Страница 21: ...onfigurable Input Configurable input port can be configured as digital signal or fuel level sensor signal digital input active when connected to B Terminal 8 Oil Pressure Input Low oil pressure or sen...
Страница 22: ...HGM1780 Automatic Genset Controller ISSUE 2013 04 03 Version1 7 Page 23 of 24 HGM1780 Automatic Genset Controller 9 OVERALL DIMENSIONS PANEL CUTOUT 78MMX66MM...