HGM1780
Automatic
Genset Controller
ISSUE 2013-04-03
Version1.7
Page 13 of 24
HGM1780 Automatic Genset Controller
6. PARAMETER RANGE AND DEFINITION
6.1 PARAMETERS CONFIGURATION (TABLE 1)
No.
Parameter
Range
Default
value
Description
P00 Start Delay
(0-3600)s
1
Time from remote start signal is
active to start genset.
P01 Stop Delay
(0-3600)s
1
Time from remote start signal is
deactivated to genset stop.
P02
Start
Attempts
(1-9) times
3
The maximum number of crank
attempts. If none of them is
successful,
the
controller
will
initiate fail to start alarm.
P03 Preheat Time (0-300)s
0
Time of pre-powering heat plug
before starter is powered up.
P04
Cranking
Time
(3-60)s
8
The time of powering up the starter
for every crank attempt.
P05
Crank
Rest
Time
(3-60)s
10
The waiting time before second
power up when engine start fail.
P06
Safety
On
Delay
(1-60)s
10
Alarms for low oil pressure, high
temperature, under speed, under
frequency /voltage, charge fail are
inactive.
P07
Start
Idle
Time
(0-3600)s
0
Idle running time of genset when
starting.
P08
Warming Up
Time
(3-3600)s
10
Warming time between genset
switch on and normal running.
P09 Cooling Time (3-3600)s
10
Radiating time before genset stop,
after it unloads.
P10
Stop
Idle
Time
(0-3600)s
0
Idle running time when genset stop.
P11
ETS Solenoid
Hold
(0-120)s
20
The time of powering up the
electromagnet
during
stop
procedure.
P12
Fail to Stop
Delay
(0-120)s
0
Time between ending of genset idle
delay and stopped when “ETS
time” is set as 0;
Time between ending of ETS hold
delay and stopped when “ETS Hold
output time” is not 0.
P13
Flywheel
Teeth
(10-300)
118
Tooth number of the engine, for
judging
of
crank
disconnect
conditions and inspecting of engine
speed.
See
the
installation
instructions.
P14
Power-on
Mode
(0-2)
0
Default: Stop Mode.
P15 Generator
(0-20.0)s
10.0
Alarm delay for generator over and