HGM1780 

Automatic 

Genset Controller 

ISSUE 2013-04-03 

Version1.7 

Page 13 of 24 

HGM1780 Automatic Genset Controller 

 

 

6.  PARAMETER RANGE AND DEFINITION 

6.1  PARAMETERS CONFIGURATION (TABLE 1) 

 

No. 

Parameter 

Range 

Default 

value 

Description 

P00  Start Delay 

(0-3600)s 

Time from remote start signal is 
active to start genset. 

P01  Stop Delay 

(0-3600)s 

Time from remote start signal is 
deactivated to genset stop. 

 

P02 

 

Start 
Attempts 

 

(1-9) times 

 

The  maximum  number  of  crank 
attempts.  If  none  of  them  is 
successful, 

the 

controller 

will 

initiate fail to start alarm. 

P03  Preheat Time  (0-300)s 

Time of pre-powering heat plug 
before starter is powered up. 

P04 

Cranking 
Time 

(3-60)s 

The time of powering up the starter 
for every crank attempt. 

P05 

Crank 

Rest 

Time 

(3-60)s 

10 

The waiting time before second 
power up when engine start fail. 

 

P06 

 

Safety 

On 

Delay 

 

(1-60)s 

 

10 

Alarms  for  low  oil  pressure,  high 
temperature,  under  speed,  under 
frequency  /voltage,  charge  fail  are 
inactive. 

P07 

Start 

Idle 

Time 

(0-3600)s 

Idle running time of genset when 
starting. 

 

P08 

Warming Up 

Time 

 

(3-3600)s 

 

10 

Warming  time  between  genset 
switch on and normal running. 

P09  Cooling Time  (3-3600)s 

10 

Radiating time before genset stop, 
after it unloads. 

P10 

Stop 

Idle 

Time 

(0-3600)s 

Idle running time when genset stop. 

 

P11 

ETS Solenoid 
Hold 

 

(0-120)s 

 

20 

The  time  of  powering  up  the 
electromagnet 

during 

stop 

procedure. 

 
 

P12 

 
 

Fail to Stop 
Delay 

 
 

(0-120)s 

 
 

Time between ending of genset idle 
delay  and  stopped  when    “ETS 
time” is set as 0; 
Time  between  ending  of  ETS  hold 
delay and stopped when “ETS Hold 
output time” is not 0. 

 
 

P13 

 

Flywheel 
Teeth 

 
 

(10-300) 

 
 

118 

Tooth  number  of  the  engine,  for 
judging 

of 

crank 

disconnect 

conditions and inspecting of engine 
speed. 

See 

the 

installation 

instructions. 

P14 

Power-on 
Mode 

(0-2) 

Default: Stop Mode. 

P15  Generator 

(0-20.0)s 

10.0 

Alarm delay for generator over and 

Содержание HGM1780

Страница 1: ...USER MANUAL HGM1780 Automatic Genset Controller Smartgen Technology...

Страница 2: ...AY DESCRIPTION 9 4 4 OPERATION INSTRUCTION 9 5 PROTECTION 12 6 PARAMETER RANGE AND DEFINITION 13 6 1 PARAMETERS CONFIGURATION TABLE 1 13 6 2 DEFINITION OF RELAY OUTPUTS TABLE 2 17 6 3 DEFINITION OF DI...

Страница 3: ...th 3 working modes that can be selected from the front panel It can detect one phase generator voltage and current can be started and stopped manually or via a remote start stop signals In case of fau...

Страница 4: ...enerator frequency Hz Generator current A Engine temperature C Oil pressure kPa Engine speed rpm Total running time H Battery voltage V Fuel level Generator voltage battery voltage engine speed temper...

Страница 5: ...uts fuel relay start relay 1 configurable output port which can be set as common alarm output fail to stop output preheat output or idle control output Parameters can be set and modified by users and...

Страница 6: ...changes every six minutes Start Relay Output 1Amp DC28V DC B power supply Fuel Relay Output 1Amp DC28V DC B power supply Programmable Relay Output 1Amp DC28V DC B power supply Digital Input Active whe...

Страница 7: ...ut down the generator and place it into its standby mode in case of alarm pressing this button will clear alarms Turn Page Confirm Using this button you can scroll pages of the LCD monitor in settings...

Страница 8: ...preheat delay begins One second before it is finished fuel output will 4 3 DISPLAY DESCRIPTION Generator phase voltage Ua frequency F Loading current la engine speed Oil pressure water temperature Liq...

Страница 9: ...seconds after the beginning of the delay preheat and ETS outputs will be activated after the end of the delay ETS output will be deactivated and fuel relay output preheat output will be deactivated be...

Страница 10: ...nly react to emergency stop signal Note Configurable output ports can be set as one of the following functions ETS output Idle output or Preheat output via PC Therefore all three functions can not be...

Страница 11: ...ry voltage warning signal is sent Only warning and not shutdown 9 Low Battery Voltage if battery voltage stays below the pre set value for 20 seconds low battery voltage warning signal is sent Only wa...

Страница 12: ...il P06 Safety On Delay 1 60 s 10 Alarms for low oil pressure high temperature under speed under frequency voltage charge fail are inactive P07 Start Idle Time 0 3600 s 0 Idle running time of genset wh...

Страница 13: ...speed falls below this value and stays so for 10 seconds this is regarded as under speed and under speed alarm shutdown signal is sent P19 Engine Over Speed 0 6000 RPM 1710 When engine speed exceeds...

Страница 14: ...attery Over Volts 12 40 V 33 0 When battery voltage exceeds this value and stays so for 20 seconds Battery Over Volts signal is send and warning without shutdown is initiated P27 Battery Under Volts 4...

Страница 15: ...ossible P37 Disconnect Engine Speed 0 3000 RPM 360 When generator speed higher than the set value starter will be disconnected P38 Disconnect Generator Freq 10 30 Hz 14 0 When generator frequency high...

Страница 16: ...isconnects after complete stop 4 Preheat control It closes before starting and opens before starter is power on 5 Closing Gens During normal operation of the generator closes the breaker 6 Reserved No...

Страница 17: ...Dongkang sensor 7 CURTIS 8 DATCON 10Bar 9 VOLVO EC 10 SGX 10Bar Digital closed and Digital open both are digital signal low or high electrical level can be selected to be active connecting to earth p...

Страница 18: ...er motor as soon as possible 2 Magnetic pickup is the magnetic equipment which be installed in starter for detecting flywheel teeth 3 When set as magnetic pickup must ensure that the number of flywhee...

Страница 19: ...y that is used for password to enter the set value Password Parameter Setting Attention 1 Please change the controller parameters when generator is in standby mode only e g Crank disconnect conditions...

Страница 20: ...rk 2 If the generator is in manual mode and crank disconnect condition is set as 2 magnetic pickup generator frequency or 5 generator frequency magnetic pickup oil pressure and generator frequency and...

Страница 21: ...onfigurable Input Configurable input port can be configured as digital signal or fuel level sensor signal digital input active when connected to B Terminal 8 Oil Pressure Input Low oil pressure or sen...

Страница 22: ...HGM1780 Automatic Genset Controller ISSUE 2013 04 03 Version1 7 Page 23 of 24 HGM1780 Automatic Genset Controller 9 OVERALL DIMENSIONS PANEL CUTOUT 78MMX66MM...

Страница 23: ...HGM1780 Automatic Genset Controller ISSUE 2013 04 03 Version1 7 Page 24 of 24 HGM1780 Automatic Genset Controller 10 TYPICAL APPLICATION...

Отзывы: