HAT880 SERIES DUAL POWER BYPASS CONTROLLER USER MANUAL
HAT880 Series Dual Power Bypass Controller 2019-07-11 Version1.1 Page 33 of 49
No.
Items
Description
33
Reserved
34
MS1 Close Control
Control the MS1 switch to close.
35
MS1 Open Control
Control the MS1 switch to open.
36
MS2 Close Control
Control the MS2 switch to close.
37
MS2 Open Control
Control the MS2 switch to open.
38
Reserved
39
Reserved
40
NEL 1 Trip
It controls NEL offload when output is active; it controls NEL
offload return (on load) when output is inactive.
41
NEL 2 Trip
42
NEL 3 Trip
43
Reserved
44
Reserved
45
MS1 On Feedback
The close status of S1 switch
46
MS2 On Feedback
The close status of S2 switch
47
S1 Genset Start
When the system type is “S1 Gen S2 Gen”, it controls the S1
genset start.
48
S2 Genset Start
When the system type is “S1 Gen S2 Gen”, it controls the S2
genset start.
49
Reserved
50
Reserved
51
Reserved
52
Reserved
53
Remote Control
Control the output via remote communication command.
54
Input 1 Status
Configurable Input status.
55
Input 2 Status
56
Input 3 Status
57
Input 4 Status
58
Input 5 Status
59
Input 6 Status
60
Input 7 Status
61
Input 8 Status
62
Reserved
63
Reserved
64
S1 Blackout
S1 power supply status
65
S1 Over Volt
66
S1 Under Volt
67
S1 Over Freq
68
S1 Under Freq
69
S1 Loss Of Phase
70
S1 Phase Seq Wrong
71
Reserved
72
Reserved
73
S2 Blackout
S2 power supply status