1 DESCRIPTION

LPC-2.P02 control panel special module is used for room temperature regulation.

Controller   is  equipped  with   temperature   sensor,   light   intensity   sensor   and   two   push   buttons:
“WARMER -  

”  and  “COOLER -  

”. To increase temperature set point “WARMER” push button is

used and to decrease “COOLER” push button is used. Temperature set point command or controller
switched off is represented with LED bar-graphs (refer to the Table 3). Light intensity sensor is
primary used for LED bar-graph intensity control, so LEDs do not disturb customer during the night if
desired.

LPC-2.P02 has many integrated settings and functions which allows adaptation to required system
and regulation diagram. Settings can be done and functions can be enabled or disabled using LPC
Manager software.

Maximum and minimum temperature set point range can be set to scale temperature set point.
Default range is between 18 °C and 24 °C.

If economic function is set, controller will start cooling when room temperature will raise above
max. temperature set point and stop when temperature will drop 1 °C below max. temperature set
point.   On   the  other   hand,  when  room   temperature  will   fall  below   min.  temperature  set   point
controller will start heating and stop when temperature will raise 1 °C above min. temperature set
point.

When four pipe (default) system is selected, controller will activate hot command when heating and
cool command when cooling is required. In case of two pipe system selection, hot command is
always   activated   when   heating   or   cooling   is   required   (depends   on   heating   or   cooling   mode
selection). For example that two pipe system, cooling mode is selected and room temperature is
higher than temperature set point on the control panel, controller will activate cooling with hot
command (cool command is off if heating or cooling is required).

In case that balcony door and/or window function is enabled and door and/or window contact is
opened,  valves for heating or cooling will be closed.

Frost protection function activates heat command when room temperature measured by the panel
drops below 5 °C. This function has priority over all control panel integrated functions.

LPC-2.P02   control   panel  is   possible   to   switch   off   using   off   command   is   set   from   LPC   Manager
software. In this case cool, heat commands are switched off.  Cool and heat commands are also
switched  off   when  temperature  measured  by   the  panel  is   inside  dead  band  (default  =   0.5   °C)
temperature values.

Control   panel   PI   regulator   output   variable   range   is   0   to   10000.   Values   from   4999   down   to   0
represents cooling and vales from 5000 up to 10000 represents heating.

Example: If proportional – P parameter (default = 25) is set to 1 and difference between measured
temperature and temperature set point is +1  °C, the control panel regulator output value will be
5100. On the other hand if the difference is -1 °C, the control panel regulator output value will be
4900.

If integral – I parameter (default = 5) is set to 1 and difference between measured temperature and
temperature set point is +1 °C, the control panel regulator output will increase every second by 100.
On the other hand if the difference is -1 °C, the control panel regulator output will decrease every
second by 100.

1

Содержание LPC-2.P02

Страница 1: ...USER MANUAL Longo programmable controller LPC 2 P02 Temperature Control panel Version 2 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 388 44 00 e mail info smarteh si www smarteh si...

Страница 2: ...Longo programmable controller LPC 2 P02 Written by SMARTEH d o o Copyright 2012 SMARTEH d o o User manual Document Version 002 July 1 2012 i...

Страница 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Страница 4: ...grammable controller LPC 2 P02 1 DESCRIPTION 1 2 FEATURES 3 3 INSTALLATION 4 3 1 Connection scheme 4 3 2 Mounting instructions 6 3 3 Module labeling 7 4 REGULATION DIAGRAM 8 5 TECHNICAL SPECIFICATIONS...

Страница 5: ...ys activated when heating or cooling is required depends on heating or cooling mode selection For example that two pipe system cooling mode is selected and room temperature is higher than temperature...

Страница 6: ...e When more modules e g LPC 2 ID1 LPC 2 ID2 LPC 2 P01 or up to four LPC 2 P02 are connected to main module splitter e g SPL 2 is also required refer to the Figure 2 LPC 2 P02 module RS485 address 0 3...

Страница 7: ...measurement room temperature 2 push buttons for temperature set point 18 LED bar graph for temperature set point Light intensity measurement LED intensity control Economic function Two four pipe heat...

Страница 8: ...Longo programmable controller LPC 2 P02 3 INSTALLATION 3 1 Connection scheme Figure 2 Connection scheme 4...

Страница 9: ...module Red LED indicates communication state On RS 485 communication fault Off RS 485 communication OK Temperature set point LED bar graph Green LEDs indicates actual temperature set point between mi...

Страница 10: ...e to the provided leveled place on the wall 2 Fasten 2 screws DIN 7981 or similar 3 mm max head height 3 mm to fix LPC 2 P01 module to its place 3 Connect interconnection cable to the interconnection...

Страница 11: ...code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 40 08 is the date code 40 week and 08 year of production Label 2 description 1 S N P02 S9 0800000003 is the serial numbe...

Страница 12: ...o programmable controller LPC 2 P02 4 REGULATION DIAGRAM Cooling Heating Speed I Speed II Speed III On Space temp C 0 0 Off Regulation dead band Temp Set point Space temp C 0 Temp Set point Space temp...

Страница 13: ...connection connector type Berg M Power consumption 60 mA Temperature measurement accuracy 1 C Dimensions W x H x D 110 x 80 x 17 mm Weight 80 g Maximum altitude 2000 m Mounting position vertical Ambie...

Страница 14: ...d system and regulation diagram Settings can be done and functions can be enabled or disabled through LPC Manager software Variables There are 22 bytes available for reading and writing from to P01 mo...

Страница 15: ...BIT2 BIT3 Balcony door status Window switch status Enab Dis balcony door cmd Enab Dis window command VWORD16 N 4 variable range Max temperature status C Fx100 0 10000 Min temperature status C Fx100 0...

Страница 16: ...setpoint C Fx100 0 10000 Min temperature setpoint C Fx100 0 10000 P regulation param 0 100 I regulation param 0 100 PI deadband parameter C Fx100 0 10000 Min light intensity param 0 100 Remote setpoin...

Страница 17: ...controller LPC 2 P02 CHANGES The following table describes all the changes to the document Date V Description 1 7 2012 002 CGP General update 13 2 2009 001 The initial version issued as LPC 2 P02 mod...

Страница 18: ...Longo programmable controller LPC 2 P02 NOTES 14...

Отзывы: