Longo programmable controller LPC-2.P02
3.2 Mounting instructions
Figure 3: Housing dimensions
Dimensions in milimeters.
All connections, module attachments and assembling must be done
while module is not connected to the main power supply.
The LPC-2.P02 module should be positioned on the wall inside the
room. It is advised to avoid direct sunlight or position near
heating/cooling source object. Round flush-mounting box (e.g. Gewiss
GW 24232), Φ60 mm is recommended for installation. A box must be
installed with screw holes in the horizontal position!
Mounting instructions:
1. Mount LPC-2.P02 module back plate to the provided leveled place on the wall.
2. Fasten 2 screws (DIN 7981 or similar, Φ3 mm,
max. head height 3 mm
) to fix LPC-2.P01
module to its place.
3. Connect interconnection cable to the interconnection connector K1. Max. allowed tractive
force is 30 N.
4. Set the correct RS-485 address (S1 switch) for LPC-2.P02 (refer to the Table 4).
5. Power (PWR) green LED should switch on according to the Table 5.
6. Mount LPC-2.P02 module front plate to the back plate.
7. Fasten the screw in the bottom carefully (not too strong), to fix the front plate to the back
plate.
NOTE: LPC-2 main module should be powered separately from other electrical appliance connected
to LPC-2 system. Signal wires must be installed separately from power and high voltage wires in
accordance with general industry electrical installation standard.
6