RTM-ATCA-F125 Installation and Use (6806800K30J)
25
Chapter 2
Hardware Preparation and Installation
2.1
Overview
This chapter describes the following:
Inspect the shipment and unpack the RTM.
Make sure environmental and power requirements are met.
Install the RTM.
2.2
Unpacking and Inspecting the RTM
The shelf should provide minimum airflow to the RTM slot according to the class B.3
requirements of the CP-TA Inter-operability document AdvancedTCA Book 1.1. This
includes the following:
2.0cfm at 25°C ambient temperature
2.8cfm at 40°C ambient temperature
4.4cfm at 55°C ambient temperature
Shipment Inspection
To inspect the shipment, perform the following steps:
1. Verify that you have received all items of your shipment:
Printed
Quick Start Guide
and
Safety Notes Summary
RTM-ATCA-F125 board
2. Check for damage and report any damage or differences to the customer service.
NOTICE
Damage of Circuits
Electrostatic discharge and incorrect installation and removal of the blade can
damage circuits or shorten its life.
Before touching the blade or electronic components, make sure that you are
working in an ESD-safe environment.