Rating for a line circuit breaker
SMA
Technologie AG
Page 40
SB1700-11:SE2006
Installation Guide
When selecting line circuit breakers, a number of load factors need to be taken into
account. These can be found in the respective data sheets.
For example, one manufacturer's circuit breaker may be designed for an ambient
temperature of 50 °C.
Load factors according to data sheet specifications:
• Reduction through permanent load >1h = 0.9
1
• Reduction when 9 circuit breakers are arranged side-by-side without
gaps = 0.77
2
• Increase in nominal current as a result of ambient temperatures of 40 °C in the
circuit breaker panel = 1.07
3
Result:
The nominal load current for the line circuit breaker is calculated as:
Ibn = 10 A x 0.9 x 0.77 x 1.07 = 7.4 A
Example for the thermal selection of a 10 A line circuit breaker with B sensitivity
with no gap between the circuit breakers:
1. Permanent loads of longer than 1 hour are possible in photovoltaics.
2. When only one circuit breaker is used, this factor = 1
3. Because the cifrcuit breakers are rated for 50 °C
Содержание SUNNY BOY 1700
Страница 2: ......
Страница 6: ...SMA Technologie AG Page 6 SB1700 11 SE2006 Installation Guide...
Страница 8: ...Foreword SMA Technologie AG Page 8 SB1700 11 SE2006 Installation Guide...
Страница 10: ...Safety information SMA Technologie AG Page 10 SB1700 11 SE2006 Installation Guide...
Страница 30: ...Opening and closing the Sunny Boy SMA Technologie AG Page 30 SB1700 11 SE2006 Installation Guide...
Страница 38: ...Replacing the varistors SMA Technologie AG Page 38 SB1700 11 SE2006 Installation Guide...
Страница 42: ...Rating for a line circuit breaker SMA Technologie AG Page 42 SB1700 11 SE2006 Installation Guide...
Страница 44: ...Contact SMA Technologie AG Page 44 SB1700 11 SE2006 Installation Guide...
Страница 45: ......
Страница 46: ......
Страница 47: ......