Mounting
SMA Solar Technology AG
12
SL6000-TEN081820
Technical Description
4.2.1 Ambient Conditions
•
The mounting location must be accessible at all times.
•
An ambient temperature between -25 °C and +50 °C ensures optimum operation.
•
Do not expose the device to direct sunlight.
•
The mounting location must be suitable for the weight and dimensions of the Smart Load.
•
Mount the device on solid surfaces only.
4.2.2 Safety Clearances
When mounting the Smart Load, make sure to observe the following safety clearances to ensure
sufficient heat dissipation.
st
Direction
Safety clearance
Sides
30 cm
Top
50 cm
Bottom
10 cm
Multiple Smart Loads installed in areas with high ambient temperatures
If necessary, increase the clearances between the individual Smart Loads and ensure that
there is sufficient ventilation. This ensures sufficient cooling.
30 cm
10 cm
SMART L
OAD
Warnin
g
Stop
Opera
tion
50 cm
30 cm