Electrical Connection
SMA Solar Technology AG
24
SL6000-TEN081820
Technical Description
5.4.2 Operation Display
You can connect an external load (e.g. energy saving lamp) to the Smart Load. It displays whether
the Smart Load is operating (green LED illuminates) and whether power is being output (green LED
flashes).
Connect the operation display to the floating relay contact X70.
Connection Procedure
1.
Loosen the lock nut of the PG screw fitting (A) and
slide it over the cable of the load.
2.
Remove the dummy plug from the cable screw
connection.
3.
Pull the cable of the load through the cable screw
connection into the inside of the Smart Load and
connect the cables to the connection terminal
"X70" (B).
4.
Tighten the lock nut on the cable screw
connection.
NOTICE!
High currents will irreparably damage the Smart Load
Observe the maximum voltage, current and power on the relay contact X70:
•
V
AC
= 230 V
•
I
AC max
= 0.5 A
•
P
AC max
= 115 W
DANGER!
Danger to life due to high voltages in the Smart Load.
•
Only start the stand-alone grid system after all cables have been connected.
A
B