14 Technical Data
SMA Solar Technology AG
Operating manual
STP15-25TL-30-BE-en-17
89
Multifunction relay
Optional
SMA Power Control Module
Optional
Surge arrester type II
Optional
Fans
Width x height x depth
60 mm x 60 mm x 25.4 mm
Noise emission, typical
≤29 dB(A)
Maximum operating altitude
3000 m
Air flow rate
≥ 40 m³/h
Torques
Upper lid screws
6 Nm ± 0.3 Nm
Screws lower lid
2 Nm ± 0.3 Nm
Screws for DC protective cover
3.5 Nm
Screw for additional grounding
5.8 Nm
SUNCLIX swivel nut
2 Nm
Data Storage Capacity
Daily energy yields
63 days
Daily yields
30 years
Event messages for users
250 events
Event messages for installers
250 events