11 Disconnecting the Inverter from Voltage Sources
SMA Solar Technology AG
Operating manual
STP15-25TL-30-BE-en-17
78
13. If the neutral conductor is connected, use an
appropriate multimeter to ensure that no voltage is
present at the AC connecting terminal block
between
L1
and
N
,
L2
and
N
, and
L3
and
N
.
Insert the test probe of the multimeter into the round
opening in the terminal.
14. Use an appropriate measuring device to ensure that no voltage is present at the AC
connecting terminal plate between
L1
and
PE
,
L2
and
PE
, and
L3
and
PE
. Insert the test
probe into each round opening of the terminal.
15. Ensure that no voltage is present between any terminal of the multifunction relay and
PE
of the
AC connecting terminal plate.
16.
DANGER
Danger to life due to high voltages in the inverter
The capacitors in the inverter take 20 minutes to discharge.
• Wait 20 minutes before opening the upper enclosure lid.
• Do not open the DC protective cover.
17.
NOTICE
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through
electrostatic discharge.
• Ground yourself before touching any component.