background image

1.  A continuous, invisible light 

beam is emitted from the 

OPTIMA Sensor.

2.  When a user enters the 

beam’s effective range, the 

beam is reflected into the 

OPTIMA’s scanning window 

and transformed into a low 

voltage electrical signal 

that activates a ten-second 

time delay circuit. The time 

delay circuit eliminates false 

operation from passers-by 

in the rest room. Once the 

time delay is completed, 

the output circuit is alerted 

and continues in a “hold” 

mode for as long as the user 

remains within the effective 

range of the sensor.

3.  When the user steps away 

from the OPTIMA Sensor, 

the loss of reflected light 

initiates an electrical “one-

time” signal that energizes 

the Solenoid Operator, and 

activates the Flushometer 

to flush the fixture. This 

occurs approximately three 

(3) seconds after indication. 

This delay is built into the 

Sensor to help prevent false 

flushing due to movement 

by the user. The circuit then 

automatically resets and is 

ready for the next user.

7

LAWS AND REGULATIONS PROHIBIT THE USE OF 

HIGHER FLUSHING VOLUMES THAN LISTED ON 

FIXTURE OR FLUSHOMETER.

!!! IMPORTANT !!!

OPERATION

TROUBLESHOOTING GUIDE

NOTE: Upon detection of the user, the red indicator light is steadily on for a period of eight seconds. When the user 

leaves the detection range, the indicator light will turn off and the Sensor initiates the flush sequence. Then the 

indicator light stops flashing and the valve flushes. The valve will flush after a three-second delay.

1. PROBLEM: Valve does not function (red light does not 

turn on when user steps in front of sensor).

 

CAUSE:  No power is being supplied to sensor.

 

SOLUTION:  Ensure that the main power is turned “ON.” Check 

transformer, leads and connections. Repair or replace as 

necessary.

 

CAUSE:  Sensor is not operating.

 

SOLUTION:  Replace Sensor.

2. PROBLEM: Valve does not function (red light flashes 

when user steps in front of Sensor).

 INDICATOR:   Red light stops flashing when user steps away 

and valve makes a “clicking” sound but does 

not flush.

 

CAUSE:  No water is being supplied to the valve.

 

SOLUTION:   Make certain that water supply is turned “ON” and the Control 

Stop is open.

 

CAUSE:   EL-128-A cartridge is fouled or jammed.

 

SOLUTION:  Turn electronic power to valve “OFF” (failure to do so could 

result in damage to the solenoid coil). Remove the solenoid 

operator from the valve and remove the 

EL-128-A cartridge. Clean and/or repair as necessary.

 INDICATOR:   The red light does not turn off when user 

steps away and the valve does NOT make a 

“clicking” sound and does NOT flush.

 

CAUSE:   EL-163-A solenoid shaft assembly is fouled or 

jammed. 

 

SOLUTION:  Turn electronic power to valve “OFF” (failure to do so could 

result in damage to the solenoid coil). Remove 

EL-101 or EL-166 nut from the solenoid operator. Remove 

the coil from the solenoid operator. Use a spanner wrench or 

pliers to remove the EL-163-A solenoid shaft assembly from 

valve. Clean and/or replace as necessary. Be sure to replace 

plunger spring when reassembling Solenoid Shaft Assembly.

3. PROBLEM:  Volume of water is insufficient to adequately 

siphon fixture.

 

CAUSE:  Control Stop is not open wide enough.

 

SOLUTION:  Adjust control stop for desired water delivery.

 

CAUSE:  Low Consumption unit is installed on Water 

Saver or Conventional fixture. 

 

SOLUTION:   Replace Diaphragm component parts of valve with kit that 

corresponds to appropriate flush volume of fixture.

 

CAUSE:  Inadequate water volume or pressure 

available from supply.

 

SOLUTION:  Increase pressure or supply (flow rate) to the valve. Consult 

factory for assistance.

4. PROBLEM: Length of flush is too long (long flushing) or 

valve fails to shut off.

 

CAUSE:  Water Saver valve is installed on Low 

Consumption fixture.

 

SOLUTION:  Replace Diaphragm component parts of valve with kit that 

corresponds to appropriate flush volume of fixture.

 

CAUSE:  Relief valve in diaphragm is not seated 

properly or bypass hole in diaphragm is 

clogged.

 

SOLUTION:  Disassemble inside Diaphragm component parts and wash 

parts thoroughly. Replace worn parts if necessary.

5. PROBLEM: Water splashes from fixture.
 

CAUSE:  Supply flow rate is more than necessary.

 

SOLUTION:  Adjust Control Stop to meet flow rate required for proper 

cleansing of the fixture.

When further assistance is required, please contact 

Sloan Technical Support at:

1-888-SLOAN-14

 

(1-888-756-2614)

.

Содержание 150 ES-SM

Страница 1: ...one 1 year for special finishes SF faucets PWT electronics and 30 days for PWT software from date of first purchase During this period Sloan Valve Company will at its option repair replace or refund...

Страница 2: ...TICAL Failure to properly position the electrical boxes to the plumbing rough in will result in improper installation and impair product performance All tradesmen plumbers electricians tile setters et...

Страница 3: ...104 to 689 kPa of water pressure THE MINIMUM PRESSURE REQUIRED TO THE VALVE IS DETERMINED BY THE TYPE OF FIXTURE SELECTED Consult fixture manufacturer for minimum pressure requirements Most Low Consum...

Страница 4: ...oupling by hand A Lubricate tailpiece o ring with water Insert adjustable tailpiece into control stop Tighten tailpiece coupling by hand Max adjustment of Sloan Adjustable Tailpiece is 13 mm IN or OUT...

Страница 5: ...ODEL 194 ES SM SHOWN 1 25 mm DIAMETER HOLE FINISHED WALL ETF 211 WALL ANCHORS INSTALLED EL 456 GASKET FLAT SIDE TOWARD WALL EL 460 WALL BRACKET OVERRIDE BUTTON MODELS 150 152 SENSOR SCREW ETF 212 6 PH...

Страница 6: ...seconds the start up mode automatically repeats itself when power is restored C The self adaptive sensor is equipped with the sentinel flush feature automatically flushes every twenty four 24 hours a...

Страница 7: ...ake certain that water supply is turned ON and the Control Stop is open CAUSE EL 128 A cartridge is fouled or jammed SOLUTION Turn electronic power to valve OFF failure to do so could result in damage...

Страница 8: ...6 F 21 1 38 mm Double Slip Elbow RB Models 152 ES SM and 190 ES SM 7 F 2 AA 1 38 mm Slip Joint Coupling RB Set of Two Model 152 ES SM 8 F 2A 1 38 mm Slip Joint Coupling RB Model 190 ES SM 9 F 2 AW 19...

Отзывы: