23
1.2.5. Authorized batteries
-
Use batteries with a capacity of
86 to 225 Ah
(daughter board jumper on ‘75’).
-
For using
38 to 225Ah battery capacities in 24V
, put daughter board jumper on ‘50’. In this case,
Imax b = 100A (mains not present) and the threshold of 13m
Ω±
10% becomes 20m
Ω±
10%.
-
For using
65 to 225Ah battery capacities in 48V
, put daughter board jumper on ‘50’. In this case,
Imax b = 100A (mains not present) and the threshold of 26m
Ω±
10% becomes 40m
Ω±
10%.
-
Use
Yuasa, Powersonic, ABT, Enersys, Effekta, or Long
brand batteries. If you would like to use another
battery brand, please have them approved.
2. Installation of your equipment
2.1.
Mounting
Note: When installing the module in the rack, the protection rating must comply with fire safety standards EN 54-4/A2:
IP30.