Congratulations, 

You have just acquired product manufactured by SLAT, and we thank you for your choice. 
This product is a Power Supply Equipment (PSE). 
This manual includes instructions for the installation, commissioning and maintenance of this equipment.  
In order for the equipment to work properly, we recommend to carefully follow these instructions. 
 
 
 

Safety precautions 

 
This equipment is designed to be connected to the 230 V public distribution network. 
To avoid any risk of electric shock, all 

INTERVENTIONS

 must be carried out with the equipment 

SWITCHED OFF

 

(upstream two-pole circuit-breaker open). 
Interventions with the equipment switched on are authorized only when it is impossible to switch the equipment off.  The 
operation must only be performed by qualified personnel. 
 

Standards, directives and protection of the environment and public health 

 
This product is compliant with LV and EMC directives (immunity and emission). It is compliant with standards EN60950-1 
(2006), EN61000-6-1 (2007), EN61000-6-2 (2006), EN61000-6-3 (2007), EN61000-6-4 (2007), and EN 55022 class B 
(2007). 
It is also compliant with the following trade standards: 
EN 54-4 (December 1997) and amendment A2 (February 2006):  Fire detection and fire alarm systems. Part 4: power 
supply equipment. 
EN 12101-10  class A (January 2006): Smoke and heat control systems. Part 10: power supplies. 
EN 60849 (August 1998): Sound systems for emergency purposes (Paragraph 5.6) 
 
CE DPC Numbers are : XXXX ( 24V) and XXXX (48V). 
They have been affixed in 2011. 
 
Slat is ISO 14001 certified since 2008. 
Slat manufactures all its products in accordance with RoHS and WEEE environmental directives.  
Slat recycles its products at the end of their service life through its recycling programme. 
 
 

    

 

 
 

Warranty 

 
Our warranty is three years from the date of delive ry (ex-works). It is strictly limited to reimbursement or replacement (at 
our discretion and without compensation of any sort) of parts recognised as faulty by our services, following return of the 
product to our premises at the buyer's expense. The replacement or repair of equipment is possible only on our premises. 
In order to allow our customers to benefit from the latest technical improvements, SLAT reserves the right to make all 
necessary modifications to its products. The battery is not included in the warranty. 

 

Содержание SON 24V 12A MS150 RACK

Страница 1: ...Code 180100016 NDU NOT100016Ba Edition 10 10 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S10 OPERATING INSTRUCTIONS P19 NOTICE D UTILISATION SON 24V 12A MS150 RACK SON 48V 12A MS150 RACK...

Страница 2: ...4 2 Installation de votre quipement 5 2 1 Fixation 5 2 2 Batteries 6 3 Raccordement 6 3 1 Plan de raccordement 6 3 2 Sp cifications de raccordement 6 4 Mise en service 7 5 Fonctionnement de l Alimenta...

Страница 3: ...alement conforme aux normes m tiers EN 54 4 d cembre 1997 et amendement A2 f vrier 2006 Syst mes de d tection incendie Partie 4 quipement d alimentation lectrique EN 12101 10 classe A janvier 2006 Sys...

Страница 4: ...limentation peut fonctionner sans courant utilisation Imin 0A 1 2 3 Fonctionnalit s et sp cifications techniques particuli res L alimentation et le syst me de sonorisation de s curit SSS doivent tre a...

Страница 5: ...des batteries de 65 225Ah en 48V positionner le cavalier carte fille sur 50 Dans ce cas Imax b 100A secteur absent et le seuil de d faut de 26m 10 passe 40m 10 Utiliser des batteries de marques Yuasa...

Страница 6: ...mm la r sistance est de 2m m o Pour une section de 16mm la r sistance est de 1 25m m o Pour une section de 25mm la r sistance est de 0 8m m o Pour une section de 35mm la r sistance est de 0 6m m Exemp...

Страница 7: ...e test batterie s effectue de la mani re suivante toutes les 30s pendant les 20 premi res minutes apr s la mise en service toutes les 15min apr s les 20 premi res minutes Si un d faut est d tect le te...

Страница 8: ...tension sur les c bles batterie doit tre identique celle de l utilisation V rifier que chaque batterie de 12Vcc pr sente une tension gale voire sup rieure 11 5Vcc R p ter la mesure apr s avoir d branc...

Страница 9: ...9...

Страница 10: ...10 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S10 OPERATING INSTRUCTIONS P19 BEDIENUNGSANLEITUNG SON 24V 12A MS150 RACK SON 48V 12A MS150 RACK...

Страница 11: ...Funktionale und technische Besonderheiten 13 1 2 4 Batteriebetrieb 13 2 Montage der Stromversorgung 14 2 1 Befestigung 14 2 2 Batterien 15 3 Anschluss 15 3 1 Anschlussplan 15 3 2 Spezifizierung der An...

Страница 12: ...950 1 2006 EN 61000 6 1 2007 EN 61000 6 2 2006 EN 61000 6 3 2007 EN 61000 6 4 2007 EN 55022 Klasse B 2007 Es ist ebenfalls nach den Normen f r den jeweiligen Einsatzbereich zertifiziert EN 54 4 Dezemb...

Страница 13: ...150A Die Stromversorgung kann ohne Verbraucherstrom arbeiten Imin 0 A 1 2 3 Funktionale und technische Besonderheiten Der Stromversorgung und die elektroakustische Sicherheitsanlage m ssen ber dasselb...

Страница 14: ...10 Um Batterien von 65 bis 225Ah f r 48V Produkt zu verwenden stellen Sie den Jumper auf der Tochterkarte auf 50 In diesem Fall Imax b 100A ohne Netz und die 26m 10 Schwelle wird zu 40m 10 Verwenden S...

Страница 15: ...10 mm betr gt der Widerstand 2 m m o Bei einem Querschnitt von 16 mm betr gt der Widerstand 1 25 m m o Bei einem Querschnitt von 25 mm betr gt der Widerstand 0 8 m m o Bei einem Querschnitt von 35 mm...

Страница 16: ...sicher angezeigt Wenn keine Batteriespannung anliegt Der Batterietest wird wie folgt ausgef hrt alle 30 s w hrend der ersten 20 min nach Inbetriebnahme alle 15 min nach den ersten 20 min Falls eine St...

Страница 17: ...5V betr gt Wiederholen Sie die Messung nachdem Sie Verbraucher und Batterie abgetrennt haben Kontrollieren Sie erneut die korrekte Funktion der Kontrollleuchten s Kap 5 Nachdem Sie alle Schritte ausge...

Страница 18: ...18...

Страница 19: ...19 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S10 OPERATING INSTRUCTIONS P19 OPERATING INSTRUCTIONS SON 24V 12A MS150 RACK SON 48V 12A MS150 RACK...

Страница 20: ...ecific features and technical specifications 22 1 2 4 Autonomy 22 2 Installation of your equipment 23 2 1 Mounting 23 2 2 Batteries 24 3 Connection 24 3 1 Connection diagram 24 3 2 Connection specific...

Страница 21: ...and EN 55022 class B 2007 It is also compliant with the following trade standards EN 54 4 December 1997 and amendment A2 February 2006 Fire detection and fire alarm systems Part 4 power supply equipm...

Страница 22: ...imum current for all the outputs is 150A the Power supply can function without load current Imin 0 A 1 2 3 Specific features and technical specifications The Power supply and the public address and vo...

Страница 23: ...For using 65 to 225Ah battery capacities in 48V put daughter board jumper on 50 In this case Imax b 100A mains not present and the threshold of 26m 10 becomes 40m 10 Use Yuasa Powersonic ABT Enersys E...

Страница 24: ...a cross section of 16 mm the resistance is 1 25 m m o For a cross section of 25 mm the resistance is 0 8 m m o For a cross section of 35 mm the resistance is 0 6 m m Example for battery cables and 1...

Страница 25: ...battery test is performed in the following manner every 30 seconds for the first 20 minutes after commissioning every 15 minutes after the first 20 minutes If a fault is detected the test is performe...

Страница 26: ...oltage on the battery cables must be identical to that of the load Check that each 12 Vdc battery has a voltage greater than or equal to 11 5 Vdc Repeat the measurement after having disconnected the l...

Страница 27: ...27...

Страница 28: ...28 SLAT 11 Rue Jean Elys e Dupuy BP66 69543 CHAMPAGNE AU MONT D OR Cedex France Tel 33 0 4 78 66 63 60 Fax 33 0 4 78 47 54 33 E mail comm slat fr http www slat fr...

Отзывы: