Jaguar Caravan Multiple and Cascading Boilers

29

An external control with 0-10 Vdc output such as Tekmar 265 or 275
could be used to operate up to 4 boilers.
One special interface control is required for operation of each boiler in
the system. Use Slant/Fin interface kit (Part no. 830130). Kit includes
interface control and 3 different harnesses needed for connection of
Tekmar control to the interface and the boiler. See figure 20. Follow
Tekmar control manual D275 for installation and operating instructions.
Install interface control next to the Tekmar control.

Some local codes require 120 volt wiring to be encased within a
flexible or non flexible electrical conduit. Local codes may require
the interface control be mounted within an approved electrical box.
Follow code requirements for the jurisdiction where the boiler is
being installed.

11.1 ELECTRICAL WIRING

11.1.1

Power supply:

A separately fused circuit is required for power connection to 
each boiler. Use standard 15 Amp fuse or breaker. Provide 
disconnect means and overload protection as required.
Boilers must be electrically grounded in accordance with the 
requirements of the authority having jurisdiction, or in the 
absence of such requirements, with the National Electrical 
Code, ANSI/NFPA 70- latest edition.

Use harness P/N 832112 (see figure 20) to connect power
supply to J1 connector of interface control. See figure 21.
Use BX cable or conduit for power supply connection. Proper 
polarity is critical for power supply connections. Reversed 
polarity will cause boiler lockout. Proper grounding is also
critical for boiler operation.

11.1.2

Interface control connection to the boiler:

Use harness P/N 832114 to connect interface J8 connector to
terminal #13 and 14 of the boiler. See figure 23.

11.1.3

Connecting Tekmar control 275 to interface control:

Use harness P/N 832115 to connect J5 connector of interface 
to Tekmar control terminal # 7 & 8 (boiler No. 1) or terminal
# 8 & 9 (boiler No. 2) or terminal 10 & 11 (boiler No.3) or
terminal 11 & 12 (boiler No. 4). See figures 20 and 21.

11.1.4

Boiler, DHW and system circulators connection:

See Tekmar application brochure A275 for different piping 
arrangements and electrical connections.

11.1.5

Outdoor and system water supply sensors:

See Tekmar manual A275 and D070 for installation instruction 
and wire connection. Use sensors supplied with the Tekmar
control or recommended by Tekmar. Tekmar control sensors 
are NTC thermistor 10 K ohm.

Note: Do not connect any other sensor(s) directly to the boilers.

11.1.6

Important:

Set the switch in the interface control to “OFF”

position. See figure 21.

11.2  SETTING BOILER’S CONTROL FOR EXTERNAL SIGNAL

Fill system with water. See Installation and Operating Instruction of
Jaguar J-390C boiler (Publication J-40). Make sure flue pipes and
air intake pipes are installed per venting application section of the
above-mentioned manual. Each boiler’s control must be properly
programmed for the system. See table 4 for setting and program-
ming the controls.

Set each boiler’s control as follow:

1. Select option #5 in “c-t” mode
2. Select option #0 in “b-A” mode
3. Check “A-t” and “A-c” in model selection and confirmation 

modes show #5, if not, set to #5.

4. Set Tekmar control: Follow Tekmar manual D275 to set control 

for selected application. Sequential or parallel modulation 
mode may be selected for boilers operation.

5. Combustion test: Run each boiler to check combustion and 

input rate. See page 37 of J-390C manual (Publication # J-40).

11.3 VIEWING BOILER WATER TEMPERATURE

Press “Select” button for viewing boiler supply water, return water
and flue gas temperature on “Temperature Display”. See table 9.

11.4 BOILER OPERATION STATUS

“Mode Display” shows status of boiler operation. See table 10
“Temperature Display” shows boiler’s water temperature, lockout or
error condition.

DANGER:

Before wiring always turn off electric power

supply. Otherwise shock or death can result.

HARNESS

PART NoN 83 2115 

HARNESS

PART No 83 2114 

HARNESS

PART No 83 2112 

 

 

 

 

 

 

Figure 20. Harnesses packed with Interface kit.

11. CONTROL USING EXTERNAL BMS SIGNAL

Содержание Jaguar Caravan J-390C Series

Страница 1: ...rdance with the National Electrical Code ANSI NFPA No 70 latest edition and all local electri cal codes The unit must be electrically grounded if an external power source is used In Canada the install...

Страница 2: ...830130000 Jaguar boilers may also be used in a heating system with a Caravan cast iron modular boiler system Since high efficiency con densing boilers only condense when the return water temperature i...

Страница 3: ...er temperature BOILER DESIGN DATA Max ASME Working Pressure 50 PSI Power Requirements 120 Volts 60 Hz 1 Phase 1 6 Amps per module not including primary circulator No of Boilers Model No L inches 1 2 3...

Страница 4: ...talled on or above carpeting All boiler components should be protected from water during installation set up operation and service Minimum clearances to combustible materials should comply with local...

Страница 5: ...Jaguar Caravan Multiple and Cascading Boilers 5 Figure 2 Typical layout of 3 Jaguar Boilers using Slant Fin Headers Minimum Clearance...

Страница 6: ...construction fully caulked and weatherstripped INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM A NON DIRECT VENT INSTALLATION 1 Air dra...

Страница 7: ...xide detectors a In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back u...

Страница 8: ...ting system installation If stainless steel vent sys tems are used follow the manufacturer s instructions in conjunction with these instructions I Non Direct Vent Installation The air for combustion i...

Страница 9: ...Jaguar Caravan Multiple and Cascading Boilers 9 Wall opening for Slant Fin vent air intake termination Height 5 3 4 Width 12 3 4 Wall thickness 3 to 14 Figure 4...

Страница 10: ...Jaguar Caravan Multiple and Cascading Boilers 10 Figure 5...

Страница 11: ...ove snow line or grade if it does not snow in area boilers are located No minimum horizontal distance between outlets or inlets Exhaust termination to extend beyond air intake prevent condensation fro...

Страница 12: ...Jaguar Caravan Multiple and Cascading Boilers 12 Figure 7...

Страница 13: ...and Cascading Boilers 13 Figure 8 Direct Venting and Air Intake Through a Roof Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to This height should be...

Страница 14: ...ness Replacing the medium on an annual basis is recommended or refer to the manufacturer s instructions for systems that are available for neutralizing condensate COMMONWEALTH OF MASSACHUSETTS SPECIAL...

Страница 15: ...10 shows typical field piped primary loops for Jaguar Multiple boiler systems Each Jaguar boiler shall be installed with a manual reset Hi Limit and a Manual Reset Low Water Cutoff being located on t...

Страница 16: ...rs 16 Figure 11 shows water primary piping using Slant Fin headers Each Jaguar boiler shall be installed with a manual reset Hi Limit and a Manual Reset Low Water Cutoff being located on the boiler si...

Страница 17: ...proceed as follows a Follow the building plans find total length of straight pipe between supply from gas meter and boiler gas header b Using data in Table 2 calculate equivalent linear length of scr...

Страница 18: ...2 700 4 700 9 700 63 130 245 500 760 1 450 2 300 4 100 8 300 56 115 215 440 670 1 270 2 000 3 600 7 400 50 105 195 400 610 1 150 1 850 3 250 6 800 46 96 180 370 560 1 050 1 700 3 000 6 200 43 90 170 3...

Страница 19: ...ure as well as determining what Jaguar boilers should operate and what their fuel input should be For details on wiring and programming using this method go to Section 10 on page 19 of this manual 2 U...

Страница 20: ...onnections Reversed polarity will cause boiler lockout Proper grounding is critical for boiler operation 10 1 2 Boiler circulator Connect boiler circulator to terminal 19 and 20 if the system is for s...

Страница 21: ...Jaguar Caravan Multiple and Cascading Boilers 21 Figure 14...

Страница 22: ...Jaguar Caravan Multiple and Cascading Boilers 22 Figure 15...

Страница 23: ...Follower boiler s in b A mode Master address is 1 and Followers addresses are 2 to 8 2 Select space heating option in c t mode of the Master boiler Mode 0 1 or 2 may be selected If mode 1 or 2 system...

Страница 24: ...perature space heating mode 1 or 2 Settable from 16 F to 122 F steps of 1 F The default value is 86 F Changing compensation slope space heating mode 1 or 2 Settable from 0 1 to 5 0 steps of 0 1 The de...

Страница 25: ...170 160 120 110 100 80 90 200 S l o p e 4 0 S l o p e 3 0 Slope 0 1 min S l o p e 2 0 Slope 0 5 S l o p e 1 2 S lo p e 5 0 m a x 40 S l o p e 1 5 S l o p e 1 0 d e f a u l t S l o p e 1 8 Maximum wate...

Страница 26: ...no func tion and are disabled 10 10 BOILER OPERATION STATUS Mode Display shows status of boiler operation Temperature Display shows water temperatures lockout error or warning conditions See table 7...

Страница 27: ...display shows system supply water Temp Domestic hot water mode Temperature display shows system supply water Temp Frost protection mode Temperature display shows system supply water Temp Lockout Alar...

Страница 28: ...resume normal operation Error Condition Temperature display indicates the error code Warning Condition Temperature display indicates the error code NOTE Blinking dot on Mode Display indicates active h...

Страница 29: ...No 1 or terminal 8 9 boiler No 2 or terminal 10 11 boiler No 3 or terminal 11 12 boiler No 4 See figures 20 and 21 11 1 4 Boiler DHW and system circulators connection See Tekmar application brochure A...

Страница 30: ...000 IS REQUIRED 0 10V DC EXTERNAL SIGNAL TEKMAR CONTROL 275 TERMINAL 7 8 BOILER 1 OR 8 9 BOILER 2 OR 10 11 BOILER 3 OR 11 12 BOILER 4 SEE TEKMAR CONTROL MANUAL D275 AND A275 WHITE BLACK HOT NEUTRAL 1...

Страница 31: ...TEMPERATURE DISPLAY Boiler is on stand by mode Temperature display shows boiler supply water Temp Heating mode Temperature display shows boiler supply water Temp Frost protection mode Temperature disp...

Страница 32: ...oper combustion at both max and min input firing rates If combustion is within the range specified on page 37 of J 390C manual clean or replace spark ignitor check power supply voltage and grounding 0...

Страница 33: ...lace the sensor 11 Water Outlet Sensor Shorted Replace the sensor 12 Water Inlet Sensor Shorted Replace the sensor 13 Flue Gas Sensor Shorted Replace the sensor 15 System Sensor Shorted Check wires go...

Страница 34: ...d have a red colored connector Check that the pumping flow direction is correct 51 Reset Button Error Try turning power supply off and on again If error returns replace the display board 52 Boiler Mod...

Страница 35: ...s at 130F This load is used to size the condensing boiler used in the hybrid system Slant Fin does publish residential baseboard and commercial radiation output ratings down to 110F water temperature...