Jaguar Caravan Multiple and Cascading Boilers
2
1. INTRODUCTION
If additional information is desired please contact your local
Slant/Fin Sales Representative or Slant/Fin Technical Services.
Slant/Fin may be found on the web at www.slantfin.com
This application manual is intended to provide the piping and control
method for applying multiple Jaguar J-390C boilers to a space heat-
ing and domestic hot water heating system. Use this manual, in
conjunction with the Jaguar J-390C Installation and Operating
Instructions, publication J-40.
The following sections of the Installation and Operating Instructions
(J-390C) must be adhered to:
1. Boiler location and foundation
2. Clearances to combustibles
3. Contamination prevention
4. Air supply and ventilation
5. Venting application and materials*
6. Water treatment
7. Condensate disposal
8. Operating instructions
9. Care and Maintenance
*Common venting of these appliances is not permitted. Direct vent
terminals cannot be clustered together or stacked vertically. Direct
vent terminals can be mounted side by side horizontally, provided
there is a 12" minimum distance between them.
There are two methods available to control J-390C Caravan boilers:
1. Jaguar link method to operate up to 8 boilers. An optional system
sensor is required for operation of this method. Supply water
system sensor (Part no. 833433000) max be ordered to
Slant/Fin boiler distributor.
2. External signal (0-10 Vdc input). Control such as Tekmar control
265 or 275 (operates up to 4 boilers). Energy Management
System may be used with this method. One optional interface
control is required for operation of each boiler in the system.
Part number for interface control kit is 830130000.
Jaguar boilers may also be used in a heating system with a
Caravan cast iron modular boiler system. Since high efficiency con-
densing boilers only condense when the return water temperature is
low, around 130 F or lower, it makes sense to use a lower cost
Caravan cast iron boiler at higher water temperature. We call a com-
bination Caravan Cast Iron Modular Boiler used in a system with a
Jaguar Multiple Boiler a “Hybrid Boiler System”. We address Hybrid
Boiler Systems within this manual.
Model
No.
Water
Content
(gal.)
Ship
Wt.
Lbs.
Vent
Conn
Air
Intake.
Water
Correction
at Boiler
Space
Btwn.
Boilers
**
Length
with
Header
**
Min.
Header
Size
J-390C 2B
J-390C 3B
J-390C 4B
J-390C 5B
J-390C 6B
J-390C 7B
J-390C 8B
4
6
8
10
12
14
16
600
900
1200
1500
2340
2730
3120
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
3-1/4
50-1/2"
77-3/4"
104-1/4"
131-1/8"
158"
184-7/8"
211-3/4"
2"
2"
3"
3"
3"
3"
3"
Table 1: Gas multiple boiler ratings and dimension/hot water model 50 psi maximum working pressure
2. RATINGS AND DIMENSIONS
Model
No.
Consists of
CSA Input
(MBH)
CSA output
(MBH)
I=B=R Net
(MBH)
Combustion
Efficiency
Boiler
Horse-
Power
No. of Htg.
Boiler
Boiler
Model No.
Max
Min
Max
Min
Max
Min
Max
Min
J-390C 2B
J-390C 3B
J-390C 4B
J-390C 5B
J-390C 6B
J-390C 7B
J-390C 8B
2
3
4
5
6
7
8
J-390C
J-390C
J-390C
J-390C
J-390C
J-390C
J-390C
780
1170
1560
1950
2340
2730
3120
110
110
110
110
110
110
110
704
1056
1408
1760
2112
2464
2816
106
106
106
106
106
106
106
612
918
1224
1530
1836
2142
2448
92
92
92
92
92
92
92
91.6
91.6
91.6
91.6
91.6
91.6
91.6
96.7
96.7
96.7
96.7
96.7
96.7
96.7
21
31.5
42
52.6
63.1
73.6
84.1
System Turndown
Model
No.
Turndown
Ratio
J-390C 2B
J-390C 3B
J-390C 4B
J-390C 5B
J-390C 6B
J-390C 7B
J-390C 8B
7 to 1
10.6 to 1
14.2 to 1
17.7 to 1
21.3 to 1
24.8 to 1
28.4 to 1
** “Length with headers allows for 3 1/4" between boiler.
Содержание Jaguar Caravan J-390C Series
Страница 10: ...Jaguar Caravan Multiple and Cascading Boilers 10 Figure 5...
Страница 12: ...Jaguar Caravan Multiple and Cascading Boilers 12 Figure 7...
Страница 21: ...Jaguar Caravan Multiple and Cascading Boilers 21 Figure 14...
Страница 22: ...Jaguar Caravan Multiple and Cascading Boilers 22 Figure 15...