background image

Jaguar Caravan Multiple and Cascading Boilers

14

7. CONDENSATE REMOVAL SYSTEM

The Jaguar J-390C boiler is equipped with a built-in condensation

drain and trap system. This system consists of two traps, one

being dedicated to the condensate produced by the boiler, and

another being dedicated to the condensate produced within the

vent piping. Both of these traps must be filled with water. This is

most easily accomplished by pouring water from a small container

into the vent connector at the top of the boiler, before the vent pipe

is attached, until the tubing loop trap in the rear of the boiler is vis-

ibly filled.  DO NOT operate the boiler without filling the trap with

water to prevent flue gas discharge into space. Periodic inspection

should be made of this assembly for deterioration of the tubing

and components, and to insure that the traps are not plugged. If

any part is plugged or appears to have excessive sediment within,

it should be removed from the drain assembly, have the obstruc-

tion cleared, refilled with water and reinstalled as before.

A 3/4” PVC tee assembly, located in the rear of the boiler jacket, is

provided to run the condensate liquid from the boiler. Connect the

plastic tubing that will be run to the drain to the bottom take-off of

the tee. Leave the top take-off of the tee open, to act as a vacuum

breaker. If the building drain is above the bottom portion of the tee,

a condensate removal pump will be required. This pump must

have an overflow switch, and be compatible with the acidic con-

densate liquid, as must all fittings and the tubing used in this con-

densate removal system. (See Figure 9).

No part of the condensate removal system can be exposed to

freezing temperatures, or any other conditions that could cause

blockage. DO NOT run drain tubing to the outside of the building.

In addition, certain jurisdictions or drain pipe materials may require

a neutralization unit to be installed in the condensate removal sys-

tem. Any piping other than plastic types will be subject to corrosion

or deterioration from the acidic condensate, which may have a pH

level as low as 3.0. A condensate filter containing lime, marble, or

phosphate chips can neutralize the condensate to a pH level

above 6.5, which is safe for all drain piping materials. (See Figure

9). The neutralizing filter medium will require periodic changing, to

ensure it’s affectiveness. Replacing the medium on an annual

basis is recommended, or refer to the manufacturer’s instructions

for systems that are available for neutralizing condensate.

COMMONWEALTH OF MASSACHUSETTS SPECIAL
REQUIREMENT

When the Jaguar J-390C is installed and used in the
Commonwealth of Massachusetts, a neutralization unit MUST be
installed in the condensate removal system.

8. WATER PIPING AND

Jaguar Multiple Boiler Systems utilize primary/secondary piping.
Jaguar boilers require a minimum of 17.5 gallons per minute water
flow rate. A primary loop circulator is factory supplied with each
Jaguar boiler, this circulator should be used in the boilers primary
loop. Listed below is a chart listing the Jaguar boiler’s pressure
drop based on GPM flow rate, this chart also lists water tempera-
ture rise based on maximum gas input.

PIPING AND WATER FLOW

Good system design addresses flow rates through boilers. It is

possible to have too little flow and too much flow. Most boiler sys-

tem designs are based on a 20˚F to 30˚F temperature rise in the

boiler when it is firing at full input.

When the flow rate is too high through a module the water flow

tends to short circuit from the return tapping to the supply tapping

of a module. When flow rate is too high the boiler efficiency may

drop and there is excess electrical consumption by the circulator.

Primary/secondary piping is required for multiple Jaguar boilers.

This method ensures that each boiler will receive the same inlet

water temperature, and only the boilers that are firing will have

water flowing through them. Each boiler must have a dedicated

circulator piped on it’s primary loop. See figures 10 and 11 for the

location of components and piping layout.

If isolation valves are installed in the individual boiler piping to the

common headers, a dedicated manual reset low water cutoff and

manual reset high limit must be installed on each boiler’s piping,

as close to the boiler as possible and beneath the isolation valves.

See figures 10 and 11.

The primary loop must have its own pump, water that is flowing in

the primary loop will not flow into the secondary circuit 

NEUTRALIZING UNIT (IF REQUIRED)

CONDENSATE PUMP (IF REQUIRED)

DRAIN INSIDE BUILDING

PLASTIC TUBING

DRAIN VACUUM BREAKER, LEAVE OPEN

Figure 9. Condensate disposal system

Flow

Rate

(gpm)

Temp

Rise

(˚F)

Boiler

Head

Loss

(Feet w.c.)

28.0

25˚

16

23.5

30˚

11.5

20.0

35˚

8.5

17.5*

40˚

7.0

Boiler Pressure Drop

* Minimum flow rate recommended.

Jaguar Multiple Boiler

System may be piped

using Slant/Fin supplied

headers or by using field

piped primary boiler

loops.

Содержание Jaguar Caravan J-390C Series

Страница 1: ...rdance with the National Electrical Code ANSI NFPA No 70 latest edition and all local electri cal codes The unit must be electrically grounded if an external power source is used In Canada the install...

Страница 2: ...830130000 Jaguar boilers may also be used in a heating system with a Caravan cast iron modular boiler system Since high efficiency con densing boilers only condense when the return water temperature i...

Страница 3: ...er temperature BOILER DESIGN DATA Max ASME Working Pressure 50 PSI Power Requirements 120 Volts 60 Hz 1 Phase 1 6 Amps per module not including primary circulator No of Boilers Model No L inches 1 2 3...

Страница 4: ...talled on or above carpeting All boiler components should be protected from water during installation set up operation and service Minimum clearances to combustible materials should comply with local...

Страница 5: ...Jaguar Caravan Multiple and Cascading Boilers 5 Figure 2 Typical layout of 3 Jaguar Boilers using Slant Fin Headers Minimum Clearance...

Страница 6: ...construction fully caulked and weatherstripped INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM A NON DIRECT VENT INSTALLATION 1 Air dra...

Страница 7: ...xide detectors a In the event that the side wall horizontally vented gas fueld equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back u...

Страница 8: ...ting system installation If stainless steel vent sys tems are used follow the manufacturer s instructions in conjunction with these instructions I Non Direct Vent Installation The air for combustion i...

Страница 9: ...Jaguar Caravan Multiple and Cascading Boilers 9 Wall opening for Slant Fin vent air intake termination Height 5 3 4 Width 12 3 4 Wall thickness 3 to 14 Figure 4...

Страница 10: ...Jaguar Caravan Multiple and Cascading Boilers 10 Figure 5...

Страница 11: ...ove snow line or grade if it does not snow in area boilers are located No minimum horizontal distance between outlets or inlets Exhaust termination to extend beyond air intake prevent condensation fro...

Страница 12: ...Jaguar Caravan Multiple and Cascading Boilers 12 Figure 7...

Страница 13: ...and Cascading Boilers 13 Figure 8 Direct Venting and Air Intake Through a Roof Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to This height should be...

Страница 14: ...ness Replacing the medium on an annual basis is recommended or refer to the manufacturer s instructions for systems that are available for neutralizing condensate COMMONWEALTH OF MASSACHUSETTS SPECIAL...

Страница 15: ...10 shows typical field piped primary loops for Jaguar Multiple boiler systems Each Jaguar boiler shall be installed with a manual reset Hi Limit and a Manual Reset Low Water Cutoff being located on t...

Страница 16: ...rs 16 Figure 11 shows water primary piping using Slant Fin headers Each Jaguar boiler shall be installed with a manual reset Hi Limit and a Manual Reset Low Water Cutoff being located on the boiler si...

Страница 17: ...proceed as follows a Follow the building plans find total length of straight pipe between supply from gas meter and boiler gas header b Using data in Table 2 calculate equivalent linear length of scr...

Страница 18: ...2 700 4 700 9 700 63 130 245 500 760 1 450 2 300 4 100 8 300 56 115 215 440 670 1 270 2 000 3 600 7 400 50 105 195 400 610 1 150 1 850 3 250 6 800 46 96 180 370 560 1 050 1 700 3 000 6 200 43 90 170 3...

Страница 19: ...ure as well as determining what Jaguar boilers should operate and what their fuel input should be For details on wiring and programming using this method go to Section 10 on page 19 of this manual 2 U...

Страница 20: ...onnections Reversed polarity will cause boiler lockout Proper grounding is critical for boiler operation 10 1 2 Boiler circulator Connect boiler circulator to terminal 19 and 20 if the system is for s...

Страница 21: ...Jaguar Caravan Multiple and Cascading Boilers 21 Figure 14...

Страница 22: ...Jaguar Caravan Multiple and Cascading Boilers 22 Figure 15...

Страница 23: ...Follower boiler s in b A mode Master address is 1 and Followers addresses are 2 to 8 2 Select space heating option in c t mode of the Master boiler Mode 0 1 or 2 may be selected If mode 1 or 2 system...

Страница 24: ...perature space heating mode 1 or 2 Settable from 16 F to 122 F steps of 1 F The default value is 86 F Changing compensation slope space heating mode 1 or 2 Settable from 0 1 to 5 0 steps of 0 1 The de...

Страница 25: ...170 160 120 110 100 80 90 200 S l o p e 4 0 S l o p e 3 0 Slope 0 1 min S l o p e 2 0 Slope 0 5 S l o p e 1 2 S lo p e 5 0 m a x 40 S l o p e 1 5 S l o p e 1 0 d e f a u l t S l o p e 1 8 Maximum wate...

Страница 26: ...no func tion and are disabled 10 10 BOILER OPERATION STATUS Mode Display shows status of boiler operation Temperature Display shows water temperatures lockout error or warning conditions See table 7...

Страница 27: ...display shows system supply water Temp Domestic hot water mode Temperature display shows system supply water Temp Frost protection mode Temperature display shows system supply water Temp Lockout Alar...

Страница 28: ...resume normal operation Error Condition Temperature display indicates the error code Warning Condition Temperature display indicates the error code NOTE Blinking dot on Mode Display indicates active h...

Страница 29: ...No 1 or terminal 8 9 boiler No 2 or terminal 10 11 boiler No 3 or terminal 11 12 boiler No 4 See figures 20 and 21 11 1 4 Boiler DHW and system circulators connection See Tekmar application brochure A...

Страница 30: ...000 IS REQUIRED 0 10V DC EXTERNAL SIGNAL TEKMAR CONTROL 275 TERMINAL 7 8 BOILER 1 OR 8 9 BOILER 2 OR 10 11 BOILER 3 OR 11 12 BOILER 4 SEE TEKMAR CONTROL MANUAL D275 AND A275 WHITE BLACK HOT NEUTRAL 1...

Страница 31: ...TEMPERATURE DISPLAY Boiler is on stand by mode Temperature display shows boiler supply water Temp Heating mode Temperature display shows boiler supply water Temp Frost protection mode Temperature disp...

Страница 32: ...oper combustion at both max and min input firing rates If combustion is within the range specified on page 37 of J 390C manual clean or replace spark ignitor check power supply voltage and grounding 0...

Страница 33: ...lace the sensor 11 Water Outlet Sensor Shorted Replace the sensor 12 Water Inlet Sensor Shorted Replace the sensor 13 Flue Gas Sensor Shorted Replace the sensor 15 System Sensor Shorted Check wires go...

Страница 34: ...d have a red colored connector Check that the pumping flow direction is correct 51 Reset Button Error Try turning power supply off and on again If error returns replace the display board 52 Boiler Mod...

Страница 35: ...s at 130F This load is used to size the condensing boiler used in the hybrid system Slant Fin does publish residential baseboard and commercial radiation output ratings down to 110F water temperature...

Страница 36: ...Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Slant Fin Corp 2011 Printed in the U S A 611 Publication No CJ 10 HWG Figure 22...

Отзывы: