29
Installation Manual
Installation Manual
3. Example: SUV4-H28/1CGA-N
Fig.6
Serial No.
Model
Indoor Unit 1
SMVH07A-2AA1NC(I)
Indoor Unit 2
SMVH07A-2AA1NC(I)
Indoor Unit 3
SMVH07A-2AA1NC(I)
Indoor Unit 4
SMVH07A-2AA1NC(I)
Table 10 Indoor Unit
a
1
b
2
c
3
d
4
4. Additional Refrigerant Charge Record
The total length of each liquid refrigerant pipe is: a+b+c+d=20+15+15+15=65m
Thus, the minimum additional refrigerant charge=(65-40)×0.022=0.55kg
(Note: no additional refrigerant is needed for the liquid pipe within 40m)
Diameter
Total Length (m)
Additional Refrigerant Refrigerant (kg)
Φ
15.9
Φ
12.7
Φ
9.52
Φ
6.35
Total
No.
Indoor Unit Model
Additional Refrigerant Refrigerant (kg)
1
2
3
.....
N
Total
Serial No.
a
b
c
d
Diameter
Φ
6.35
Φ
6.35
Φ
6.35
Φ
6.35
Length
20
15
15
15
Table 11 Liquid Refrigerant Pipe
Table 12 Indoor Unit
Table 13 Refrigerant Pipe