6.6 Pipe expanding method
Improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe according to the following steps:
A: Cut the pipe
Con
fi
rm the pipe length according to the distance of indoor unit and outdoor unit. Cut the required pipe with pipe cutter.
pipe
pipe cutter
uneven
leaning
burr
B: Remove the burrs
Remove the burrs with shaper and prevent the burrs from getting into the pipe.
pipe
shaper
downwards
C: Put on suitable insulating pipe
D: Put on the union nut
Remove the union nut on the indoor connection pipe and outdoor valve; install the union nut on the pipe.
union pipe
pipe
E: Expand the port
Expand the port with expander.
expander
hard
mold
pipe
Note:
"A" is different according to the diameter, please refer to the sheet below:
Outer diameter(mm)
A(mm)
Max Min
Ф
6 - 6.35(1/4")
1.3
0.7
Ф
9.52(3/8")
1.6
1.0
Ф
12-12.7(1/2")
1.8
1.0
Ф
15.8-16(5/8")
2.4
2.2
F: Inspection
Check the quality of expanding port.
If there is any blemish, expand the port again according to the steps above.
smooth
surface
the length is equal
improper expanding
leaning
damaged
surface
crack
uneven
thickness
Содержание SUV2-H18/3CFA-N
Страница 3: ...Summary and Features Outdoor Unit 18K 24K 28K ...
Страница 4: ...36K 42K ...
Страница 20: ...16 Construction Views Construction Views 24K 28K Unit mm 920 990 790 394 370 426 610 ...
Страница 21: ...17 Construction Views Construction Views 36K 42K Unit mm 950 1020 997 368 340 396 590 ...
Страница 23: ...19 Schematic Diagram Schematic Diagram SUV2 H18 1CFA N 24K ...
Страница 42: ...38 Troubleshooting Troubleshooting Model 28K ...
Страница 44: ...40 Troubleshooting Troubleshooting Model 36K ...
Страница 47: ...43 Troubleshooting Troubleshooting Model 42K ...