10
Technical User Guide
DA 74C Winch Motor
4.1.3
Setting the Jumper
Jumper setting on the PCB to give the DA 74C the desired function.
Figure 9: Jumper setting
O.C. = Open Collector (transistor output)
ON/OFF
Control v24 V => Close.
Control voltage 0 V => Open.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 1.8 V (15 degree opening) => relay turns ON.
STEPLESS
Control v24 V/0 V => Open. 0 V/24 V => Close.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 9.2 V (85 degree opening) => relay turns ON.
0-10 V ANALOG
The control voltage increases together with the opening degree. 2.3 V = 23% open.
The feedback signal increases together with the opening degree.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 0.5 V => relay turns ON.
ON/OFF REVERSE
Control v24 V => Close.
The feedback signal increases together with the opening degree 0.25 V= closed=90°.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 1.8 V (15 degree opening) => relay turns ON.
ANALOG
REVERSE
The control voltage increases reverse the opening degree. 2.3 V = 77% open.
The feedback signal increases reverse the opening degree.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 0.5 V => relay turns ON.
STEPLESS
– 15°
Control v24 V/0 V => Open. 0 V/24 V => Close.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 1.8 V (15 degree opening) => relay turns ON.
STEPLESS
REVERSE
Control v24 V/0 V => Open. 0 V/24 V => Close.
Feedback signal > 0.5 V => O.C. turns ON.
Feedback signal > 9.2 V (85 degree opening) => relay turns ON.
90º
0º
90º
0º
REVERSE