Replacement Procedures
Service Manual
SKOPE VF Series
Ambient Probe
The ambient probe is attached to a bracket on the side of the condenser
assembly.
To replace the ambient probe
Figure 17: Ambient probe
Ambient probe
1. Disconnect the cabinet from the power supply.
2. Remove the sign assembly (see page 53).
3. Move into a position to gain clear access to the freezer unit.
4. Gain access to the controller terminals at the rear of the electronic controller
and disconnect the ambient probe cable (see “Controller Wiring” on page 73
for termination information).
5. Trace the probe cable onto the condenser assembly and remove, cutting
cable ties as necessary.
6. Following the same path, fit the new probe cable (and probe) and secure in
place with cable ties.
7. Reassemble and test run to confirm correct operation.