Operation
User Manual
SKOPE BME ActiveCore
2
Operation
Automatic Start-Up
After the cabinet has been positioned in a suitable place, plug it in and check
the following activity.
Lighting
The cabinet interior lighting will consist of either LED tube side lights, or LED
modular shelf and side lighting. The cabinet may also be fitted with a top
sign assembly which is lit by an LED tube.
The cabinet lighting will automatically switch on and off depending on chiller
usage. The lights can also be manually switched on and off using the light
button on the electronic controller faceplate (see page 12).
LED Tube Side
Light
Cabinets with LED tube side lights are fitted with LED tube/s which can be
replaced without moving shelves or product (see page 18 for replacement
instructions).
LED Modular
Shelf and Side
Lighting
Cabinets with LED modular shelf and side lighting are lit by shelf lights
mounted on the front of the shelves (two lights per shelf), and LED side
lights. LED modular light components are all non-serviceable items and
must not be tampered with in any way. If a component is suspected of being
faulty, a service call should be arranged so that a replacement component
can be fitted.
Sign Light
Cabinets with a lit sign are fitted with an LED tube, located inside the top sign
assembly. In the event of sign light failure, a service call should be arranged
so that a replacement LED tube can be fitted.
Item
Activity
Electronic
Controller
An electronic controller runs the chiller and is visible behind
the front panel. The display panel first flashes start-up
messages before stabilising on the cabinet temperature.
Lighting
The lights that illuminate the sign and cabinet interior will come
on approximately five seconds after the chiller is turned on.
Compressor and
Condenser Fan
The compressor and condenser fan will start approximately
one minute after the chiller is turned on.
To verify, listen for the compressor and check that the
COMPRESSOR light is lit on the electronic controller. The
compressor and condenser fan will turn off when the product
temperature reaches 2°C, and on again when it
reaches about +4°C (SKOPE BME ActiveCore default
settings).
Evaporator Fan
The evaporator fan starts approximately three seconds after
the compressor and condenser fan. To verify, check that the
FAN light is lit on the electronic controller.