7
(C) Copyright 2010-2014 SKD System AB
reset;
Reset dynamic data. Reset is equivalent to turn off power and turn on power again. Permanent data are not changed
by reset.
restore;
Restore permanent node data to factory defaults. This includes: ip address, gateway address, node name, sensor
timers, autofuse settings.
LAN-configuration
h-lan;
Help LAN configuration commands
lanconf;
Read LAN control interface data.
lanip;
Read ip address
lanip:[ip];
Set ip address. To activate, enter command lanactivate; To return to factory defaults, use restore; command,
alternatively: restore can be done in some product models by pushing manual switch for 10sec (See User Manual) Example:
lanip:192.168.1.222;
New ip address
langw;
Read gateway ip address
langw:[ip];
Set gateway ip address. To activate, enter command lanactivate; Example:
langw:192.168.1.1;
New gateway
address
lanmask;
Read ip mask
lanmask:[ip];
Set ip mask. To activate, enter command lanactivate; Example:
lanmask:255.255.255.0;
New MASK address
lanactivate;
Activate new ip address, new gateway address and/or new ip mask. The command activates only ip, gw and/or
mask which do no have value 0.0.0.0
landhcp;
Read DHCP client status, 0 = not active, 1 = active
landhcp:[dhcp];
Activate/deactivate DHCP client. After this command, reset the node, to activate the change. Example:
landhcp:1;
Activate DHCP client
AC-switch
h-acsw;
Help AC-switch commands
acsw;
Read AC outlet states
acsw:[id]-[state];
Set AC outlet/outport id = 1 to off (0) or on (1) Example:
acsw:1-1;
Turn on AC1. acsw:1-0
E-meter
h-emeter;
Help E-meter commands
emeter;
Read E-meter status and measurement results
emeter:[id]-[activate];
Start/Stop KWH meter Example:
emeter:1-1;
Start KWH meter. emeter:1-0
AutoFuse
h-autofuse;
Help AutoFuse configuration commands
autofuselimit:[id]-[Ampere];
Set autofuse threshold, in Ampere. Range 0 ... 16A Example:
autofuselimit:1-12;
Set Autofuse
threshold to 12 Ampere
autofuselatency:[id]-[Ampere];
Set autofuse current latency, in Ampere. Range 0 ... 16A Example:
autofuselatency:1-12;
Set Autofuse current latency to 12 Ampere
autofuse;
Read autofuse status
autofuse:[id]-[activate];
Enable/Disable fuse Example:
autofuse:1-1;
Enable autofuse1. autofuse:1-0
Presence sensor
h-psensor;
Help presence sensor commands
psensortimer:[id]-[sec];
Set time limit, in seconds, for presence sensor. Range 0 ... 9999sec. Timer value is preserved at
reset Example:
psensortimer:1-1800;
Set timer to 1800 sec
psensor;
Read presence sensor data
psensor:[id]-[status];
id = [1,2] status = [0,1] 0=OFF, 1=ON. Activate/deactivate presence sensor. Presence: 0=Absent
1=Present 2=Sensor deactivated. Example:
psensor:1-1;
Activate Sensor1, psensor:1-0
Manual switch
SW1
Turn AC1 on/off when AC1 is not controlled by Sensor1.
AC1 is controlled by Sensor1 if LED1 is Red.