Operation Guide     

Model TM46 

 

SiteSage Thermostat 

 

 

 

 

 

 

 

  

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MENU 

COOL 

MODE 

72 H 

AUTO 

FAN 

HOLD 

75

2

 

75 C 

4:30 PM 

SYS

 

Off

 

Fan Off 

Hold 

Temperature 

Setting 

 

  Warmer 

 

 

 Cooler 

Fan Mode 

Selection 

Heating/Cooling 

Mode Selection 

Run/Hold 

Mode Selection 

Menu 

Selection 

Room 

Temperature

Setpoints 

Backlite Display 

Main Thermostat Screen 

Minimized Display  

 

Press any button to return to the main thermostat screen 

75 

  

  

  

 

 

  

  

  

Thermostat Name 

Zone Name 

Mi-Wi Signal 

Strength 

 

DCN: 140-02302-01 

Page 12 

 

Setting the heating or cooling temperature setpoint 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

 

 If the System Mode is OFF, pressing either the Up or Down buttons will take you 

to the System Mode screen.  You must first set an operating mode before you can 

set or change the setpoint. 

 

!

  To change the Heat Setpoint you must be in the Heating mode, to change the Cool 

Setpoint you must be in the Cooling mode.  If you are in Auto mode, the mode of the 

last system call will be the setpoint screen displayed. 

 

Setpoint Push:

  

Note that you cannot lower the cooling setpoint below the heating 

setpoint.  The thermostat will “push” the heating setpoint lower if you try to lower the 

cooling setpoint below the heating setpoint.  It maintains a 3 degree separation between 

the heating and cooling setpoint.  The same is true for raising the heating setpoint above 

the cooling setpoint.  Again the thermostat will “push” the cooling setpoint up to maintain 

the 3 degree separation. 

 

Lower Temperature 

Raise Temperature 

Press a button to 

go to the setpoint 

change screen  

Setpoint change screen 

Press “DONE” button to set the setpoint and exit back 

to the main thermostat screen or wait for the screen to 

automatically time out. 

Press the up or down arrow buttons to 

set the desired temperature setpoint 

HEATING SETPOINT 

Pressing the up 

or down buttons 

will increment the 

setpoint 1 degree.  

Press and hold 

the button to 

ramp the setpoint. 

75 

MENU 

HEAT 

MODE 

HOLD 

64H 

82C 

AUTO 

FAN 

Sys Off 

  

70 

Done 

  

  

 

 

  

  

Thermostat Name 

 

Содержание TM46

Страница 1: ...re to set the change over type in the Installer Settings menu to C O Type w Heat Otherwise leave it set to w Cool DCN 140 02302 01 Page 2 Standard HVAC System G Fan W1 Heat Stage 1 Y1 Compressor Stage 1 R 24VAC Return C 24VAC Common Thermostat Connection Y2 Compressor Stage 2 W2 Heat Stage 2 Optional 24R Connection for single transformer HVAC Systems RC and RH are jumpered together on thermostat b...

Страница 2: ...d Stage Cool Enable second stage cooling outputs If you have a single stage cooling system leave this set to N If you have a two stage cooling system set to Y to enable 24RC W1 24RH W2 O RS1 RS1 RSC 24C Cooling 24V Fan Cooling stage 1 Cooling stage 2 Remote Sensor 2 Remote Sensor 2 Sensor shield 24VAC Com 24V Heating Aux Heating Change Over Valve Remote Sensor 1 Remote Sensor 1 Sensor shield Remot...

Страница 3: ...N these settings affect HVAC system operation and should only be changed by qualified HVAC service technicians Installer Settings Menu Items Display Lock Options Y or N Default N Y Display LOCKED N Display UNLOCKED Allows you to lock or unlock the thermostat buttons When the buttons are locked you can still access the main menu but you will not be allowed to select any menu options The Installer S...

Страница 4: ... or accept setpoints higher that this maximum Options 40F to 109F 4C 43C Default 90F 32C Min Cool SP Sets the minimum cooling setpoint value Will not ramp or accept setpoints lower than this minimum Options 44F to 113F 6C 45C Default 60F 15C Min Run Time MRT Sets the minimum run time before a heating cooling cycle turns off Sets heating cooling cycle time Prevents rapid cycling Options 1 9 Minutes...

Страница 5: ... 2 Type 3 Type 3 RS2 Location Indoors or Outdoors In Out In Restore Defaults factory defaults Yes or No No Exit no USER SETTINGS Filter Service Submenu Service Interval Disabled 100 4000 hrs 300 Maint Service Submenu Maint Interval Disabled 100 4000 hrs 3000 Screen Timeout to minimized screen 0 20 120 sec 0 0 off will not timeout RH Setpoint 40 70 50 F C Settings F or C F Sensor Calibration Submen...

Страница 6: ...n Auto mode the mode of the last system call will be the setpoint screen displayed Setpoint Push Note that you cannot lower the cooling setpoint below the heating setpoint The thermostat will push the heating setpoint lower if you try to lower the cooling setpoint below the heating setpoint It maintains a 3 degree separation between the heating and cooling setpoint The same is true for raising the...

Страница 7: ...ors Optional Fan Mode Fan Cycler If the Fan Cycler feature is enabled in the Installer Setup the additional fan mode Cycle will be shown in the Fan Mode menu This mode cycles the fan on and off continuously for fresh air ventilation according to the settings in the Installer Setup System Status Indicators When the main thermostat screen is displayed the on screen labels indicate the following Syst...

Страница 8: ... menu item to load the Comfort schedule into the thermostat Confirmation screen will be displayed for Yes No entry Preset EnergyMiser This is a preset schedule with deeper setbacks Select this menu item to load the EnergyMiser schedule into the thermostat Confirmation screen will be displayed for Yes No entry Day Schedule Screen When you select the Heat and Cool Schedule menu item the day schedule...

Страница 9: ...een and the current number of degrees of offset being applied typically 0 If the sensor s actual temp is 75 with 0 degrees of offset and you want it to display 76 then press to add 1 deg and it will indicate 76 in the display with 1 deg offset You can refresh the info on this screen by pressing the right hand blank button When you close this screen it may take a few seconds for the temperature dis...

Страница 10: ...it does not respond immediately due to another call that has recently completed and the MOT delay timer is preventing the system from restarting The MOT delay time can be adjusted in the Installer Settings menu of the thermostat There is a minimum of 5 minutes delay to assure compressor protection Note The MOT status is shown in the thermostat System Status on screen labels DCN 140 02302 01 Page 2...

Страница 11: ...quipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Any chan...

Отзывы: