background image

DCN: 140-02302-01 

Page 19 

 

 

Setup Button  (not labeled on screen) 

To setup the thermostat to work with your HVAC system, press and hold the “Setup” 

button.  This will take you to the installation setup screen.  See installation instructions for 

proper settings. 

 

Status Button (not labeled on screen) 

Press and hold this button.  A system status screen will show the output status of the 

thermostat relays. 

 

Done Button 

Press Done to exit the thermostat Info screen back to the main menu. 

 

Mi-Wi Network Info and Thermostat Name  

The MiWi Network Info screen displays the current configuration of the network. 

 

The information displayed is: 

 

 

Network – 

will show Installed or Not Installed, indicating whether thermostat 

registration at 

www.sitesage.net

 is complete.  

 

MAC – 

the MAC address of the thermostat. Record this number with the zone 

the thermostat serves and the heating/cooling equipment name controlled by the 

thermostat.  

 

GW MAC –

 the MAC address of the SiteSage Gateway the Thermostat is 

connected to.

 

 

RSSI –

 a measure of the strength of the Mi-Wi connection to the SiteSage 

Gateway; an RSSI less than 100 indicates a poor connection.

 

 

Once registered at 

www.sitesage.net

 the name given to the thermostat in the SiteSage 

software appears at the top of the thermostat on the home screen.  

 

 

Thermostat Operation 

 

Minimum Run Time (MRT) 

The thermostat has a Minimum Run Time after the start of any heating or cooling call.  

This minimum run time assures even heating and cooling cycles.  The MRT delay will keep 

the system on even if reaches setpoint or you change the setpoint to a temperature that 

would satisfy the call, until the MRT expires.   Changing the Mode to OFF will cancel the 

MRT and the system will turn off immediately. The MRT can be adjusted in the Installer 

Settings menu of the thermostat. 

 

Note:  The MRT status is shown in the thermostat System Status on-screen labels

.   

 

Minimum Off Time (MOT)   

The thermostat has a Minimum Off Time after any heating or cooling call is finished.  This 

delay prevents rapid heating/cooling cycles and also provides “short cycle protection” for 

compressor calls.  This delay may be noticeable when you change a setpoint and it does 

not respond immediately due to another call that has recently completed and the MOT 

delay timer is preventing the system from restarting.  The MOT delay time can be adjusted 

in the Installer Settings menu of the thermostat.  There is a minimum of 5 minutes delay to 

assure compressor protection. 

 

Note:  The MOT status is shown in the thermostat System Status on-screen labels. 

 

DCN: 140-02302-01 

Page 20 

 

Remote Sensors 

 

The thermostat has two remote temperature sensor inputs. 

 

Remote Sensor RS1

.  When connected, the thermostat will use the RS1 remote sensor 

instead of the internal sensor.  Temperature displayed will be the RS1 temperature. 

 

Remote Sensor RS2

.  Selectable sensor location: Inside or Outside.  RS2 can be 

selected to be an inside remote sensor or an outside remote sensor in the Installer 

Settings/Remote Sensors menu item. 

 

RS2 Location set to IN (Inside) (default setting).  When set to Inside remote type, RS2 is 

an averaging sensor that is averaged with the internal thermostat temperature sensor.   If 

RS1 is also attached, RS2 will be averaged with the RS1 sensor instead (since it replaces 

the internal sensor). 

 

RS2 Location set to OUT (Outside).   When set to, RS2 will be used to display outside 

temperature on the thermostat. 

 

Remote sensor configurations 

 

 

Sensors Used  

 

Remote 

Sensors 

attached 

Internal 

 

RS1 

RS2 Type 

IN 

RS2 Type 

OUT 

Sensor Function 

None 

  

  

  

Use internal sensor for room temperature 

 

RS1   

  

  

                                                                                                                             

Use RS1 sensor for room temperature.  

Internal sensor not used 

RS2   

  

  

Average internal sensor with RS2 sensor and use 

the average for room temperature 

RS1 and  

RS2   

  

  

Average RS1 and RS2 sensors and use the 

average for room temperature 

RS2   

  

  

  

X  

Internal sensor used for room temperature 

RS2 sensor used for outside temperature  

RS1 and 

RS2   

  

  

RS1 sensor used for room temperature  

RS2 sensor used for outside temp temperature 

 

Viewing Remote Sensor Temperatures 

The actual temperatures being reported by the remote sensors can be viewed in the 

Sensor Calibration Screen in the Main Menu/User Settings menu item. 

 

 

 

 

 

 

 

 

 

Done 

   

Sensor Calibration 

  

+

 

Internal     (75)     0 

Remote 1  (78)     1 

Remote 2  (n/a)    0  

Outside     (85)     0 

Sensor temperature is displayed in the parenthesis (75).  n/a is displayed when 

no sensor is connected.  0 can be -7 to +7 calibration offset 

If Sensor 2 location is selected as “Outside”, then sensor temp is displayed in 

the Outside (85) parenthesis. 

Содержание TM46

Страница 1: ...re to set the change over type in the Installer Settings menu to C O Type w Heat Otherwise leave it set to w Cool DCN 140 02302 01 Page 2 Standard HVAC System G Fan W1 Heat Stage 1 Y1 Compressor Stage 1 R 24VAC Return C 24VAC Common Thermostat Connection Y2 Compressor Stage 2 W2 Heat Stage 2 Optional 24R Connection for single transformer HVAC Systems RC and RH are jumpered together on thermostat b...

Страница 2: ...d Stage Cool Enable second stage cooling outputs If you have a single stage cooling system leave this set to N If you have a two stage cooling system set to Y to enable 24RC W1 24RH W2 O RS1 RS1 RSC 24C Cooling 24V Fan Cooling stage 1 Cooling stage 2 Remote Sensor 2 Remote Sensor 2 Sensor shield 24VAC Com 24V Heating Aux Heating Change Over Valve Remote Sensor 1 Remote Sensor 1 Sensor shield Remot...

Страница 3: ...N these settings affect HVAC system operation and should only be changed by qualified HVAC service technicians Installer Settings Menu Items Display Lock Options Y or N Default N Y Display LOCKED N Display UNLOCKED Allows you to lock or unlock the thermostat buttons When the buttons are locked you can still access the main menu but you will not be allowed to select any menu options The Installer S...

Страница 4: ... or accept setpoints higher that this maximum Options 40F to 109F 4C 43C Default 90F 32C Min Cool SP Sets the minimum cooling setpoint value Will not ramp or accept setpoints lower than this minimum Options 44F to 113F 6C 45C Default 60F 15C Min Run Time MRT Sets the minimum run time before a heating cooling cycle turns off Sets heating cooling cycle time Prevents rapid cycling Options 1 9 Minutes...

Страница 5: ... 2 Type 3 Type 3 RS2 Location Indoors or Outdoors In Out In Restore Defaults factory defaults Yes or No No Exit no USER SETTINGS Filter Service Submenu Service Interval Disabled 100 4000 hrs 300 Maint Service Submenu Maint Interval Disabled 100 4000 hrs 3000 Screen Timeout to minimized screen 0 20 120 sec 0 0 off will not timeout RH Setpoint 40 70 50 F C Settings F or C F Sensor Calibration Submen...

Страница 6: ...n Auto mode the mode of the last system call will be the setpoint screen displayed Setpoint Push Note that you cannot lower the cooling setpoint below the heating setpoint The thermostat will push the heating setpoint lower if you try to lower the cooling setpoint below the heating setpoint It maintains a 3 degree separation between the heating and cooling setpoint The same is true for raising the...

Страница 7: ...ors Optional Fan Mode Fan Cycler If the Fan Cycler feature is enabled in the Installer Setup the additional fan mode Cycle will be shown in the Fan Mode menu This mode cycles the fan on and off continuously for fresh air ventilation according to the settings in the Installer Setup System Status Indicators When the main thermostat screen is displayed the on screen labels indicate the following Syst...

Страница 8: ... menu item to load the Comfort schedule into the thermostat Confirmation screen will be displayed for Yes No entry Preset EnergyMiser This is a preset schedule with deeper setbacks Select this menu item to load the EnergyMiser schedule into the thermostat Confirmation screen will be displayed for Yes No entry Day Schedule Screen When you select the Heat and Cool Schedule menu item the day schedule...

Страница 9: ...een and the current number of degrees of offset being applied typically 0 If the sensor s actual temp is 75 with 0 degrees of offset and you want it to display 76 then press to add 1 deg and it will indicate 76 in the display with 1 deg offset You can refresh the info on this screen by pressing the right hand blank button When you close this screen it may take a few seconds for the temperature dis...

Страница 10: ...it does not respond immediately due to another call that has recently completed and the MOT delay timer is preventing the system from restarting The MOT delay time can be adjusted in the Installer Settings menu of the thermostat There is a minimum of 5 minutes delay to assure compressor protection Note The MOT status is shown in the thermostat System Status on screen labels DCN 140 02302 01 Page 2...

Страница 11: ...quipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Any chan...

Отзывы: