background image

 

  

 

1

 

 

IV.   OPERATING INSTRUCTIONS ................................................................................ 34 

 

4.1 

Introduction .......................................................................................................... 34 

4.2 

Operating ups in online mode .............................................................................. 34 

4.2.1 

Starting ups from a completely shut down position ..................................... 34 

4.2.2 

Shutting down the ups ................................................................................ 34 

4.2.3 

Switching the UPS from a normal  

operation to maintenance bypass condition .............................................. 35 

4.2.4 

Switching the UPS from a maintenance  

bypass condition to normal operation ....................................................... 35 

4.3 

UPS Behavior During mains outage .................................................................. 35 

 
 

V.   MAINTENANCE ....................................................................................................... 36 
 

5.1 

Scheduled maintenance .................................................................................... 36 

5.2 

   Daily checks ..................................................................................................... 36 

5.3 

Weekly checks .................................................................................................. 36 

5.4 

Annual Maintenance .......................................................................................... 37 

5.5 

Storage conditions and transportation of ups ..................................................... 37 

 

 

VI.    FAULTS AND TROUBLESHOOTING .................................................................... 38 

 

 

6.1. 

General Procedure for fault checking and troubleshooting ................................ 38 

6.2. 

Before calling service ........................................................................................ 38 

 
 

VII.    UPS REMOTE MANITORING AND CONTROL .................................................... 39 

 

7.1. 

Using Serial Port ............................................................................................... 39 

7.2. 

Serial Communication port connection cable ..................................................... 39 

7.3. 

Modem connection ............................................................................................ 40 

 

7.3.1 

Hardware configuration ............................................................................... 40 

 

7.3.2

 Functioning Principle .................................................................................. 40 

 

7.3.3

 Modem Programming Procedure ................................................................ 40 

 

 

7.3.3.1

 Smart modem (SM) programming ................................................... 40 

 

7.3.4

 Modem – UPS Connection Cable ............................................................... 41 

7.4. 

Dry contact (

ınterface

) connections ................................................................... 41 

7.5. 

Remote monitoring panel connection of UPS .................................................... 41 

 

VIII.  EFFICIENT USAGE OF UPS IN TERMS OF ENERGY CONSUMPTION

 ............. 42 

 
 
 
 

 
 
 
 
 

 

Содержание LION100K

Страница 1: ...20 kVA 3 Phase In 3 Phase Out Sinercom srl Headquarter Via G Cappalonga 9 A 00043 Ciampino Rm Italy tel 39 06 79800323 fax 39 06 79814644 Factory Via Cascina Secchi 247 4b 24040 Isso BG tel 39 0363 93...

Страница 2: ......

Страница 3: ...Power Cables 10 2 5 Safety Earth 10 2 6 Cable Connection Procedure 10 2 6 1 Description of Connection Terminals of the UPS 11 2 7 Battery Installation 12 III FRONT PANEL 14 3 1 Introduction 14 3 2 Fr...

Страница 4: ...5 4 Annual Maintenance 37 5 5 Storage conditions and transportation of ups 37 VI FAULTS AND TROUBLESHOOTING 38 6 1 General Procedure for fault checking and troubleshooting 38 6 2 Before calling servic...

Страница 5: ...C power is disconnected To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cables only after signalin...

Страница 6: ...nternal voltage and frequency regulating software which ensures that its output to the critical load is maintained within close tolerances independent of voltage and frequency variations on the mains...

Страница 7: ...ble polarity battery with common terminal Automatic and manual battery test and battery temperature compensation features 3 separate maintenance clock counters Battery charge with current limiting Aut...

Страница 8: ...Switch S4 F7 F8 F9 Output Switch Fuse S5 F10 F11 F12 Battery Switch Fuse K1 Rectifier Input Contactor K2 Inverter Output Contactor Rectifier Charger 3 PHASE MAINS I P Battery Dual Polarity Maintenanc...

Страница 9: ...ack outs when it is connected to either static or maintenance bypass supply 1 2 2 OPERATING CONDITIONS OF UPS UPS may be in one of the following operating conditions A Normal Operation If Mains supply...

Страница 10: ...mmunation Socket DB9 female Relay Output contacts Batt circuit breaker output and input Generator input Temperature sensor Relay 2 S7 On off switch S1 AC input F1 F2 F3 S3 maintenance by pass S2 By Pa...

Страница 11: ...00 Load up to 94 Load Crest Factor 3 1 Output Voltage THD linear load 3 Overload 125 Load 10min 150 Load 1min BATTERY Total Number 60 blocks 12V 2x30 serial 60 batteries external Float Charge Voltage...

Страница 12: ...age is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit packa...

Страница 13: ...ations are for guideline purposes only and are superceded by local regulations and codes of practice 2 5 Safety Earth The safety earth cable must be connected to the earth BUS BAR and bonded to each c...

Страница 14: ...ution panel NOTE The earth and the neutral connections must be in accordance with the local rules WARNING Note that the Input Neutral N1 MUST also be connected to K10 terminal 2 6 1 Description of con...

Страница 15: ...t at reasonable temperatures to obtain efficient battery operation In general a minimum space of 10 mm must be left on all vertical sides of the battery block A minimum clearance of 20 mm should be al...

Страница 16: ...13 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...

Страница 17: ...oad on bypass indicator lamp L3 Input voltage indicator lamp L4 Rectifier run pilot lamp L5 Battery operation indicator lamp L6 Load on UPS indicator lamp L7 Output switch on indicator lamp There are...

Страница 18: ...l measurements ENTER EXIT ALARM LOGS UPS LOG RECORD Page1 ENTER CLEAR LOG Page1 ENTER EXIT INFORMATION RS232 Comm 1 2 Page1 Maximum UPS power Page1 Nominal voltage and frequency Page1 Inverter firmwar...

Страница 19: ...ut command Page3 ENTER EXIT PASSWORD Getting service code Page1 Type service password Page1 Type user password Page1 ENTER EXIT ADJUST in English Group adjustments Automatic settings Inverter factory...

Страница 20: ...alarm messages Up previous page down next page MEASUREMENTS INPUT Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page MEASUREMENTS BYPASS Level 2...

Страница 21: ...1 222 223 V Phase to neutral measured AC UPS output voltages Iout 00 0 00 0 00 0 A Measured AC RMS load currents Current alarm messages Up previous page down next page MEASUREMENTS OUTPUT Page 2 Level...

Страница 22: ...n next page MEASUREMENTS DC Page 3 Level 3 Backup time 0000 min Calculated remaining time Current alarm messages Up previous page down next page MEASUREMENTS DC Page 4 Level 3 ENTER EXIT ENTER exit to...

Страница 23: ...32 activity indicator for com1 and com2 MAX Power 60000 VA Maximum ups output power as VA Nom 220 050 220 050 Nominal input output voltage and frequency Current alarm messages Up previous page down ne...

Страница 24: ...adjust BL DELAY CLOSED Backlight delay BL DIM CLOSED Back light half option selection Current alarm messages Up upper line down next line or options ENTER select an option OPTIONS LCD OPTIONS Page 3 L...

Страница 25: ...PTIONS COMMUNICATION OPTIONS Page 4 Level 3 RELAY 7 Left and right buton relay function selection option RELAY 8 Left and right buton relay function selection option RELAY 9 Left and right buton relay...

Страница 26: ...PTIONS Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page Level 3 Bypass options VAT transfer ON OFF Page1 Gen set bypass ON OFF Page1 Gen set sy...

Страница 27: ...ND ON OFF Left and right disable alarm buzzer MIMIC LED TEST ENTER lamp test Current alarm messages Up upper line down next line or options ENTER apply command COMMAND MENU Page 4 Level 2 ENTER EXIT E...

Страница 28: ...on recorded maximum power ENTER FAULT RESET ENTER fault reset Current alarm messages Up upper line down next line SERV CE MENU Page 2 Level 2 FAN MAINT 01000 Remaining hours to FAN maintenance BAT MAI...

Страница 29: ...or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related module We saw the message in the A00 INV FAULT XXXX or R00 PFC FAULT XXXX format Numbers shown in X de...

Страница 30: ...s INV CODE 0XXX Current inverter mod le status code A00 INV FAULT XXXX Hata XXXX fault occured at the inverter module CALL SERVICE A01 O P OVERCURRENT Alarm IGBT saturation alarm on inverter module A0...

Страница 31: ...upted A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC A37 AC CURR LIMIT Warning Inverter output current limited A38 FUSE FAILURE Warning Any fuse in UPS is blowned A39 PSP FAILURE Ala...

Страница 32: ...frequency is normal R06 OVERTEMPERATURE Overtemperature at rectifier module call service R07 BLACKOUT There is a short blackout at the AC input voltage of the UPS this is temporary wait until the AC...

Страница 33: ...if hot use air cooling system If batteries are internal check the UPS ambient temperature if normal call service L02 TH2 TEMP HIGH L04 TH2 TEMP LOW UPS TH2 cabinet inside temperature is out of tolera...

Страница 34: ...nt is normal A07 SHORT CIRCUIT There is short circuit at the output of the UPS check installation and loads A08 ON MAINTENANCE The maintenance by pas switch of the UPS is ON 1 position there is a lock...

Страница 35: ...ds the mesage will be cleared A26 BATTERY LOW The DC BUS or battery voltage of the UPS is low still UPS is running but DC voltage is going down If this alarm occures during mains failure it means that...

Страница 36: ...very high higher then 150 the UPS limited the output current This status is temporary but if continues call service A38 FUSE FAILURE Call service A39 PSP FAILURE Call service A43 USER LOGIN User logg...

Страница 37: ...n ATTENTION BYPASS VOLTAGE WILL BE CONNECTED TO THE OUTPUT TERMINALS OF UPS WHEN THE ON OFF SWITCH S7 IS SWITCHED ON 4 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC R...

Страница 38: ...dy for uninterruptable operation When the mains voltage is not available R02 LINE FAILURE message appears on LCD display Sound warning on and off is heard at the same time UPS continues to supply the...

Страница 39: ...NCE counter BATTERY MAINTENANCE counter GENERAL MAINTENANCE counter This type of protective maintenance prevents small problems turning up to big failures LION Series UPS has been designed to require...

Страница 40: ...one at least two times a year in order to provide safe and efficient operation your UPS and battery group UPS generates a warning message when the maintenance time has expired 5 5 Storage Conditions a...

Страница 41: ...ed while trying to indicate the error Fault determination First step is to record the messages indicator panel LEDs operating parameter values and last status of switches This must be done before Fixi...

Страница 42: ...TEST until battery low alarm CANCEL battery test Turn off UPS output voltage immediately SHUTDOWN Turn off UPS output voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN and turn...

Страница 43: ...hone and listen the modem sound NOTE Not all the modems are compatible with the command set on UPS In such a case modem should be set by connecting a PC 7 3 2 Functioning Principle The remote operator...

Страница 44: ...perature sensor input 12 Function programmable relay contact output 2 14 Function programmable relay contact output 3 16 Function programmable relay contact output 4 ATTENTION Maximum 42Vac or 60Vac v...

Страница 45: ...sources 2 Every electric powered device is designed appropriate to a defined power level Device capacity should be selected according to its load requirement for an efficient operation 3 Ensure to ope...

Страница 46: ......

Отзывы: