5
1.2 Design Concept
S1 (F1-F2-F3)
: Rectifier Input Switch / Fuse
S2 (F4-F5-F6)
: Bypass Input Switch / Fuse
S3
: Maintenance Bypass Switch
S4 (F7-F8-F9)
: Output Switch / Fuse
S5 (F10-F11-F12)
: Battery Switch / Fuse
K1
: Rectifier Input Contactor
K2
: Inverter Output Contactor
Rectifier /
Charger
3 PHASE
MAINS I/P
Battery
(Dual Polarity)
Maintenance
Bypass Switch
Static
Bypass
S2
(F4-F5-F6)
S1
(F1-F2-F3)
S5
(F10-F11-F12)
S3
S4
(F7-F8-F9)
Inverter
K2
3 PHASE
AC Output
K1
̃
-
-
̃
SB
Содержание LION100K
Страница 2: ......
Страница 16: ...13 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...