20

Go to the 

FUNCTION

 page and locate “

Floor config

”, then, configure it through the Up/Down key 

 

With

” or “

Without

”.

[Notes]

(a) It will be memorized upon power failure.
(b) When it is set to be “with”, "Normal temp" is defaulted and unconfiguralbe; when it is set to "Without", "High 
temp" is defaulated and hot water temperature can be set freely.
(c) “Floor config” can be changed only when the unit is turned off.

2.2.30 Remote Sensor

It can be configured to be “

With

” or “

Without

” based on the actual condition.

[Operation Instructions]

Go to the 

FUNCTION

 page and locate “

Remote sensor

”, then, configure it through the Up/Down key 

 

, “

With

” or “

Without

”.

[Notes]

(a) It will be memorized upon power failure. 
(b) “

T-room ctrl

” can be selected only when the 

Remote Sensor

 is set to “

With

”.

2.2.31 Air removal

This function is intended to expel air inside the water system with only the water pump in operation when 

installation of the unit is finished.

[Operation Instructions]

Go to the 

FUNCTION

 page and locate “

Air removal

”, then, configure it through the Up/Down key 

 

On

” or “

Off

”.

[Notes]

(a) It will not be memorized upon power failure. 
(b) It can be set only when the unit is turned off.

2.2.32 Address

It is used to identify the unit in use in the central control system.

[Operation Instructions]

Go to the 

FUNCTION

 page and locate “

Address

”, then, configure it through the Up/Down key 

 

 to 

set the address.

[Notes]

(a) It indicates the address of the control and is intended for the group control.
(b) It will not be memorized upon power failure. 
(c) The address range is [1,125] and [127,253]
(d) The default address is 1 for the initial use.

2.2.33 Gate-Controller(Gate-Ctrl.)

It can be configured to be “

On

” or “

Off

” based on the actual condition.

[Operation Instructions]

Go to the 

FUNCTION

 page and locate “

Gate-Controller

”, then, configure it through the Up/Down key 

 

, “

On

” or “

Off

”.

[Notes]

(a) When it is activated, the control will check the card is inserted or not. If inserted, the control will run 
normally; if not, the control will turn off the unit and back to the homepage. In this case, any key operation 
is ineffective (except for the combined key operation), or a dialogue box will pop up, warning"

Keycard 

uninserted!

". 

(b) It will not be memorized upon power failure.

2.3 Parameter Setting (Parameter Set)

2.3.1 User Parameter Setting

Содержание SMH-100IRA? SMH-140IRA

Страница 1: ...AIR TO WATER HEAT PUMPS SMH 100IRA SMH 140IRA MONOBLOCK INVERTER...

Страница 2: ...Original instructions...

Страница 3: ...nual are only for reference 2 In order to make the product better we will continuously conduct improvement and innovation We have the right to make necessary revision to the product from time to time...

Страница 4: ...View 1 1 1 Keys Indicating LEDs 1 1 2 Standby Page and Homepage 2 2 Operation Instructions 3 2 1 On Off 3 2 2 Function Setting 4 2 3 Parameter Setting Parameter Set 20 2 4 View 23 2 5 General Setting...

Страница 5: ...n when some fault occurs 4 Left key It is intended to move the cursor left 5 Up key It is intended to modify the setting state or value of the selected parameter 6 Menu key It is intended to call out...

Страница 6: ...is any error 4 T water out It indicates the actual leaving water temperature 5 T outdoor It indicates the actual outdoor environment temperature 6 Key lock It indicates if the key lock is activated o...

Страница 7: ...vated it will be deactivated by pressing the ON OFF key and then press the ON OFF key again to start the unit e ON OFF operation will be memorized by setting Memory to be On at the GEN setting page Th...

Страница 8: ...The function key no 3 or no 4 can be used for switch pages After the setting is finished by pressing the Menu key the control will back to the homepage or by pressing the Return key the control will...

Страница 9: ...e changed by the user When the Floor config is set to Without this setting can be changed freely 5 Cool hot water Cool hot water Cool Hot water Cool When the water tank is unavailable this function wi...

Страница 10: ...cation error and the ON command can be performed only when 40 seconds have been expired When it is set to Air hot water hot water can be performed even though the thermostat is off 20 Assistant heater...

Страница 11: ...ation Instructions At the equipment OFF state access to the FUNCTION page and then move through the Left Right key the cursor to the Mode whose characters will be reversed then press the Up Down key t...

Страница 12: ...High 35 C 95 F Normal Lower limit water out temperature at the weather dependent mode for heating Lower WT Heat 40 C 104 F High 25 C 77 F Normal b This setting will be memorized upon power failure 2...

Страница 13: ...Save a pop up window will pop up to remind if you are determined to save this setting If so press the OK key If not press the Cancel key to not save this setting 4 When the setting is saved the contr...

Страница 14: ...anitize the water tank by raising the water temperature to 70 C under which the legionella will die immediately When this function is activated the sanitation data and start time is configurable Opera...

Страница 15: ...ons 1 At the homepage by pressing the Function key access to the FUNCTION page and then locate where Weekly timer is by switching pages after that press OK key to go to the WEEKLY TIMER setting page 2...

Страница 16: ...T water out will be the default value 35 c When Weekly timer has been set successfully water heating solar heater or water tank heater is available and water temperature set point is higher than 50 at...

Страница 17: ...C 1 C Heat Room temperature for heating RT heat 18 30 C 20 C 1 C 2 2 13 Clock Timer This function will make the unit run with certain modes in certain periods within a day based on the user s actual d...

Страница 18: ...Instructions 1 At the homepage by pressing the Function key access to the FUNCTION page and then locate where Temp timer is after that press OK key to go to the TEMP TIMER setting page 2 At the TEMP T...

Страница 19: ...ress OK to confirm the configuration or press Cancel to cancel this configuration 4 After saving the configuration this page will automatically back to the FUNCTION page with the cursor stayed at Sola...

Страница 20: ...nly when the unit is OFF When it is intended to activate this function with the unit being ON a dialog box will pop up warning Please turn off the system first b When this function has been activated...

Страница 21: ...er and Temp timer also cannot be activated or will be deactivated if being activated d At the Emergency mode commands from the Thermostat is ineffective e At the Emergency mode only one running mode b...

Страница 22: ...minate water heating when the thermostat is turned off g Under the Without mode the unit will run based on the mode set by the controller h The status of the thermostat can be changed only when the un...

Страница 23: ...will be memorized upon power failure 2 2 26 Water Tank It can be configured to be With or Without based on the actual condition Operation Instructions Go to the FUNCTION page and locate Water tank th...

Страница 24: ...or Off Notes a It will not be memorized upon power failure b It can be set only when the unit is turned off 2 2 32 Address It is used to identify the unit in use in the central control system Operati...

Страница 25: ...o press the OK key if not press the Cancel key to not save this setting Notes For those parameter which default value vary by different condition the value will set to default when the condition chang...

Страница 26: ...e Weather depedent mode changes it will back to the default value 13 Lower limit room temperature at the Weather dependent Mode for heating Lower RT Heat 18 21 C 64 70 F 18 C 68 F Once setting of the...

Страница 27: ...mit water out temperature at the weather dependent mode for cooling Lower WT Cool 7 14 C Without underfloor coil 18 21 C With underfloor coil 45 57 F Without underfloor coil 64 70 F With underfloor co...

Страница 28: ...h component HP pump SL pump Swimming pump Viewable Components Full Name Displayed Name Status Compressor running state Compressor On Off Fan 1 running state Fan 1 On Off Fan 2 running state Fan 2 On O...

Страница 29: ...ction temperature discharge temperature water in temperature water out temperature etc Operation Instructions 1 At the VIEW page select Parameter and then press the OK key to go to the Para View page...

Страница 30: ...rors follow the same way b If the total no of errors exceed six other errors should be viewed by switching pages through Last and Next c Any one among IDU auxiliary heater 1 error IDU auxiliary heater...

Страница 31: ...imming 31 Remote room sensor 1 T Remote Air1 F3 32 Remote room sensor 2 T Remote Air2 33 Heat pump water flow switch HP Water SW Ec 34 Solar kit water flow switch SL Water SW F2 35 Swimming pool water...

Страница 32: ...ng Solarsuperheat F6 2 4 4 Version View VERSION At the version view page the user is enabled to see the version of the program and the protocol Operation Instructions 1 At the VIEW page select Version...

Страница 33: ...for 1 minute and will lights on where there is any key operation 2 5 1 Time Date Operation Instructions 1 At the homepage by pressing GEN access to the GENERAL SET page Then select Time Date at this...

Страница 34: ...y key operation will become ineffective Operation Instructions At the homepage by pressing the up and down keys simultaneously for 5 seconds it is able to activate or deactivate this function When it...

Страница 35: ......

Страница 36: ...ces you are making an important contribution to the protection of our environment Please ask your local council where your nearest disposal station is located In case of quality problem or other pleas...

Отзывы: