23
18
Upper limit room
temperature at the
Weather-dependent
Mode for cooling
Upper RT-Cool
24~30°C
75~86°F
27°C/81°F
Once setting of the
"Weather-depedent
mode" changes, it will
back to the default value.
19
Lower limit room
temperature at the
Weather-dependent
Mode for cooling
Lower RT-Cool
18~23°C
64~73°F
22°C/72°F
Once setting of the
"Weather-depedent
mode" changes, it will
back to the default value.
20
Upper limit water-out
temperature at the
Weather-dependent
Mode for cooling
Upper WT-Cool
15~25°C
[Without underfloor
coil]
22~25°C
[With underfloor coil]
59~77°F
[Without underfloor
coil]
72~77°F
[With underfloor coil]
15°C/59°F [Without
underfloor coil]
23°C/73°F[With
underfloor coil]
It will back to the default
setting when Weather-
dependent Mode setting
changes.
21
Lower limit water-out
temperature at the
weather-dependent
mode for cooling
Lower WT-Cool
7~14°C
[Without underfloor
coil]
18~21°C[With
underfloor coil]
45~57°F[Without
underfloor coil]
64~70°F[With
underfloor coil]
7°C/45°F[Without
underfloor coil]
18°C/64°F[With
underfloor coil]
It will back to the default
setting when Weather-
dependent Mode setting
changes.
22
Temperature
deviation for cooling
ΔT-Cool
2~10°C
36~50°F
5°C/41°F
23
Temperature
deviation for heating
ΔT-Heat
2~10°C
36~50°F
10°C/50°F
24
Temperature
deviation for heating
water
ΔT-hot water
2~8°C
36~46°F
5°C/41°F
25
Room temp variation ΔT-Room temp
1~5°C
36~41°F
2°C/36°F
26
Run time
Run time
1~10min
/
3min[Without underfloor
coil]
/
5min[With underfoor
coil
]
27
Solar kit-start temp
variation
T-Solar start
10~30°C
50~86°F
15°C/59°F
28
Solar battery-max.
temp
SL- battery
Max
90~130°C
194~266°F
110°C/230°F
2.4 View
At the view pages, the user is enabled to view the unit’s running state, running parameters, errors, version of the