7
28
Solar heater
Solar heater
With/Without
Without
When it is set to "With", this
function can be activated/timed/
deactivated. When it is set to
"Without", this function will be
deactivated.
29
Floor config
Floor config
With/Without
With
If it is set to “With”, "Water
out temperature control" is
defaulted to be “Normal temp”.
For “Without”, it is “High temp”
and can be set freely . This
setting is unavailable when the
unit is OFF.
30
Remote sensor
Remote sensor
With/Without
Without
When it is set to “Without”,
the “Control state” will be
automatically changed to
“T-water out”.
31
Air removal
Air removal
On/Off
Off
/
32
Address
Address
[1~125]
[127~253]
1
/
33
Gate-Controller
Gate-Ctrl.
On/Off
Off
/
2.2.1 Mode
It enables the user to select the run mode of the unit. When the water tank is not prepared, then only
Cool
and
Heat
modes are available. When the water tank has been prepared and
Water Tank
is set to “
With
” through the
wired controller (see Section 2.2.26 for more details), then
Cool
,
Heat
,
Hot water
,
Heat
+ hot water
, and
Cool
+
hot water
modes are available. In this case,
Heat +
hot water
or Cool + hot water can be given priority. (see
Section 2.2.5 and 2.2.6 for more details), which is the default setting before delivery.
[Operation Instructions]
At the equipment OFF state, access to the FUNCTION page and then move through the Left/Right key
the cursor to the “Mode” whose characters will be reversed, then press the Up/Down key
to
modify its setting.
[Notes]
(a) The “
Heat
” mode is defaulted when the unit is energized for the first time.
(b) The running mode is allowed to be changed only when the unit is not in operation. If it is done with the unit
being on, a window will pop up, warning “
Please turn off the system first
”.
(c) When the water tank is disabled, only the ‘
Heat
” or the “
Cool
” mode is allowed.
(d) When the water tank is enabled, “
Cool
”, “
Heat
”, “
Hot water
”, “
Cool+hot water
”, “
Heat+hot water
” is
allowed.
(e) For the heat pump, the “
Cool
” mode is allowed; for the heating only unit, “
Cool+ Hot water
” and “
Cool
” are
unallowable.
(f) This setting can be memorized upon power failure.
2.2.2 Control State (Ctrl. state)
It enables the user to configure the control state to leaving water temperature or room temperature.
[Operation Instructions]
Go to the
FUNCTION
page and locate
Ctrl. state
, then, configure it through the Up/Down key
.
[Notes]
(a) If “
Remote sensor
” is set to “
With
”, “
T-out water
” and “
T-room
” are available. While if “
Remote Sensor
” is
set to “
Without
”, only “
T-out water
” is selectable.
(b) This setting will be memorized upon power failure.
2.2.3 Fast Hot Water
When hot water is needed urgently, this function can be configured to be “On”, In this case, the heat pump and