background image

17

warning indication. For example, a detector identifies an accumulation of smoke or heat that may have resulted from a fire,

but the alarm threshold has not yet been reached. A “Pre-alarm Warning”message will be displayed, but the signalling

appliances and LEDs do not respond. Proceed as follows:

1. Accept the event (see Section 1.4). Note the location of the event.
2. Remedy the cause of the condition indicated, taking care to determine whether the warning was

caused by a fire condition or a trouble (device or system fault, etc.). Monitor the system to determine

whether or not the detector develops an alarm condition some time later on. If a fire condition is pres-

ent, an alarm will be triggered, regardless of whether the pre-alarm event was accepted or not.

2.5.2. Alarm Verification

Detector Alarm Verification Mode----

CONSYS programming allows certain detectors to be programmed for “Alarm

Verification Mode.”When a detector on a 2-way data circuit (ISN-512I/P or ISA-412I/P) is confirmed into the Alarm band, it

enters a Verification mode. An “ALARM VERIFYING”event is generated and a RETARD--RESET--RESTART period of 30

seconds is started. After the RETARD-RESET-RESTART period ends, a 60-second CONFIRMATION time period begins.

If, at any time during this CONFIRMATION period, the device is re-confirmed into an ALARM, an ALARM will be raised. If

the device is not confirmed into the ALARM band during the CONFIRMATION period, then the Verification is concluded an

the device returns to the Non-Verification mode.

IXA-500DM Module with Alarm Verification—

IXA-500DM Conventional Detector Module may have its “Verification”

function enabled. Once the control unit has displayed an “Alarm Verifying” message, a 10-second “reset” period is

generated. After the reset period, a 60-second “confirmation”period is begun. If, during the confirmation period, the control

unit determines that a detector is in alarm, an “Alarm”condition will be triggered. The system will not return to standby for at

least 60 seconds after reset; and then, only if there are no alarms.

Note:

When the system returns to standby, no message is

displayed, except the usual date/time display.

If there are no other troubles or events, the system will return to the normal, or Standby mode. The display will return to the

normal date/time display.

NOTE: Alarms override trouble conditions. Any trouble conditions that

have been overridden by an alarm will now be displayed.

Alarm Verification Counters—

A record is kept of the number of times a particular addressable point (detector or detector

Module) has entered into an alarm verification sequence. When the alarm verification counter for a particular device

exceeds a threshold count (set by CONSYS) a trouble event is generated indicating that the point in question may require

maintenance (for example, a dirty detector). System RESET restores all verification counters to zero.

2.6. Positive Alarm Sequence (PAS)

NFPA 72 codes allow for an alarm response called Positive Alarm Sequence (PAS). PAS (enabled through CONSYS)

allows trained personnel to investigate an alarm occurrence in a specified manner before activation of the alarm indicating

apliances. The TFX-500M/800M Positive Alarm Sequence operates as follows:

1. The signal from a detector (smoke/heat) selected for the purpose (PAS) shall be acknowledged at the

control unit by trained personnel within fifteen (15) seconds of annunciation in order to initiate the

alarm investigation phase. If the signal is not acknowledged in 15 seconds, all normal building and

remote signals will be activated afutomatically.

2. Trained personnel will have upto 180 seconds during the alarm investigation phase to determine the

fire condition and reset the system. If the system is not reset during this investigation phase, all nor-

mal building and remote signals will be activated automatically.

3. If a secnodd selected automatic fire detector is actuated during the alarm investigation phase, all nor-

mal building and remote signals will immediately be activated automatically.

4. If any other initiating device is actuated, all nurmal building and remote signals will be activated auto-

matically.

5. The system shall provide means to bypass the positive alarm sequence.

2.7. Fault Overflow

When there are multiple fault conditions in the TFX-500M/800M system (more than 15), a “Fault Overflow”condition

occurs. When this happens, individual trouble/fault information may not be reliable until the fault overflow condition is

removed.

firealarmresources.com

Содержание TFX-500M

Страница 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...

Страница 2: ...This page is blank firealarmresources com...

Страница 3: ...IONAL LTD COMPANY 835 Sharon Drive Westlake Ohio 44145 G i AUTOCALL TFX 500M and TFX 800M Fire Control System Operator s Manual Publication Number 850516 Issue 3 Revision A September 1997 firealarmres...

Страница 4: ...hority having jurisdiction For further information contact AUTOCALL TFX Products 835 Sharon Drive Westlake Ohio 44145 Telephone 440 871 9900 Facsimile 440 871 8320 WARNING This equipment generates and...

Страница 5: ...TFX 500M and TFX 800M AUTOCALL TFX 500 and TFX 800 CONSYSrProgramming Guide Publication Number 850463 Programming the TFX Fire Control System via a personal computer only authorized and trained person...

Страница 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...

Страница 7: ...ormal Operation 13 2 3 1 Access Levels 14 2 3 2 Initial Condition 14 2 3 3 Event Monitoring 14 2 4 Multiple Events 16 2 4 1 Event Priority 16 2 4 2 Alarm Resound Always Option 16 2 4 3 Bell Map Alarm...

Страница 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...

Страница 9: ...tting and operating the AUTOCALL TFX 500M and AUTOCALL TFX 800M fire alarm system requires the use of the special key Make sure you have one available Only authorized personnel may reset a fire contro...

Страница 10: ...NE TROUBLE LED yellow O KEYSWITCH F ALPHANUMERIC DISPLAY P PANEL SILENCE touch button G NO DELETE touch button Q ALARM SILENCE touch button H SCROLL UP touch button R SYSTEM RESET touch button I SCROL...

Страница 11: ...ARM LED red K POWER LED green B TROUBLE LED yellow L QUIT touch button C SUPERVISORY LED yellow M FAST ACCESS touch button D ZONE ALARM LED red N NUMERIC touch pad E ZONE TROUBLE LED yellow O KEYSWITC...

Страница 12: ...u do What happens Look at the AUTOCALL TFX 500M 800M control panels to see Alarms Listen for Alarm signals 1 Two red FIRE ALARM LEDs light 2 Red ZONE ALARM LED s flash 3 Buzzer sounds 4 Alarm bells ho...

Страница 13: ...panels to see SUPERVISORY lights and messages Listen for SUPERVISORY signals 1 Yellow SUPERVISORY LED light 2 Buzzer sounds a pulsing tone 3 Display gives SUPERVISORY message Read the display to deter...

Страница 14: ...ROUBLE lights and messages Listen for TROUBLE signals 1 Yellow TROUBLE LED light 2 Yellow ZONE TROUBLE LED s light 2 Buzzer sounds a pulsing tone 3 Display gives TROUBLE message Read the display to de...

Страница 15: ...TOR DISPLAY MODULE QUIT 23 JAN 94 22 17 02 1 Enter your passcode number or use Special Passcode 0911 and press YES ENTER The display will respond with the following message Do you want to accept event...

Страница 16: ...12 o clock position Allows access to touchpad functions Press ALARM SILENCE 1 Buzzer will change from constant to pulsing tone for alarm change from pulsing to off for trouble or supervisory alarm al...

Страница 17: ...p Zone 2 A48 001 FIRST SILENCE ALARMS RESET SYSTEM To reset the system 1 Accept events 2 Insert the key and turn the keyswitch to Enable 12 o clock position position 3 Press ALARM SILENCE to silence t...

Страница 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...

Страница 19: ...follows Figure 2 1 AUTOCALL TFX 500M 800M Keyswitch Positions Key FIRE TROUBLE SUPERVISORY POWER PANEL SILENCE ALARM SILENCE SYSTEM RESET DRILL ENABLE OFF LAMP TEST TURN CLOCKWISE TO 12 O CLOCK POSITI...

Страница 20: ...is pressed RESET Pressing RESET while the keyswitch is in the Enable position resets the system following the occurrence of an alarm or other event The system can only be reset after the signalling d...

Страница 21: ...LL TFX 500M 800M control panel to be operated from a remote location The front panel of the Remote Ops Dis panel is identical to that of the AUTOCALL TFX 500M 800M see Figure 1 2 or 1 3 It shows the s...

Страница 22: ...s 0001 to 9999 2 3 2 Initial Condition At initial power up the AUTOCALL TFX 500M 800M display shows the following message until the power up sequence is completed TFX 500 or TFX 800 initialising initi...

Страница 23: ...ed in the order of priority Event priority is as follows 1 FIRE EVACUATE 6 FAULTS ADDRESSABLE POINTS 2 FIRE ALERT 7 FAULTS CLEAR 3 WARNINGS 8 RESET SILENCE 4 FAULTS SYSTEM 9 PRINTER OFF LINE 5 SUPERVI...

Страница 24: ...the following will occur a Outstanding Events counter will be incremented b Signalling appliances will not be reactivated 3 If the bells horns strobes signalling appliances HAVE been silenced and the...

Страница 25: ...there are no other troubles or events the system will return to the normal or Standby mode The display will return to the normal date time display NOTE Alarms override trouble conditions Any trouble c...

Страница 26: ...el to remain in a Trouble condition The fire control system may not respond properly to a fire alarm condition Contact yourl Fire Protection Systems representative or Technical Services 835 Sharon Dri...

Страница 27: ...data Print Menu s Open VFP Available only at Cus tomer Manager access level and above Other options not shown are available at higher access levels Virtual Front Panel Menu Only available on ThornNet...

Страница 28: ...uence s Y Next Menu View Unrestored Events t Y Do you want to view log N or Events Display or No Events Found If there are unrestored events in the system the display will show the event s in the foll...

Страница 29: ...d in order of priority the highest priority first Press t to move forward through the log Press s to move backward through the log When either the beginning OR end of the log is reached an End of Log...

Страница 30: ...he zones may be viewed A 1 indicates that a zone or a point in the zone IS isolated a 0 indicates that it is not Thus for the example given below all or part of zones 1 and 16 are isolated Pressing QU...

Страница 31: ...ay be set Proceed as follows 1 Select the Set Time option The display will respond with the following message Enter time as HHMMSS In this display HH Hours MM Minutes SS Seconds The cursor will blink...

Страница 32: ...want to test system Do you want to sounders Do you want to isolate points t Y N or s Point solo test zone Zonal solo test Solo test Point solo test Solo test Sounder solo test Note During Solo Test S...

Страница 33: ...ontact monitor modules or detector monitor modules to be tested without raising an alarm Warning This function will disable the point s under test 1 Select the Solo Test Point option from the menu The...

Страница 34: ...ly 2 seconds every 30 seconds 4 Walk around the site to all indicating appliances Check for correct operation of the indicating appliances 5 When all the indicating appliances have been checked press...

Страница 35: ...mple Zone 1 has been isolated POINT ISOLATED 3rd Floor 12 15 00 23 Jan 90 Non Addressable Pnt Zone 1 Isolate Point 2 Way Data Circuits Only Individual devices may be isolated using their addresses Pro...

Страница 36: ...menu options sequence shown in Figure 3 8 will be displayed Figure 3 8 De Isolate menu options sequence s s t Y N or t Y N or Y Next Menu Do you want to de isolate pnts de isolate zone sensors only de...

Страница 37: ...ETE The display will return to that shown in Step 1 above 8 Once the correct loop has been chosen the display will respond with the following message Point no 0 none Yes all 9 Enter the address of the...

Страница 38: ...s in this menu allow the contents of the Event Log or the results of a Solo Test to be printed Figure 3 10 Print Data menu options sequence s s t Y N or t Y N or Y Do you want to print data Print poin...

Страница 39: ...in the summary table contain the following parameters Table 3 2 Printer message parameters and abbreviations Abbreviation Parameter Address Zone loop and point number Dev Device type code number Con...

Страница 40: ...ation point type number The MAXIMUM number of events that the log can hold is 150 Asking for more than this number will cause the AUTOCALL TFX 500M 800M control panel to display invalid try again 5 Th...

Страница 41: ...eceived attention Periodic System Checks The system can be configured to display a warning message accompanied by an audible alert when the system test is due This feature must be configured by an aut...

Страница 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...

Страница 43: ...This page is blank firealarmresources com...

Страница 44: ...rinted in the U S A Specifications and other information shown were current as of publication and are subject to change without notice 2001 Simplex Time Recorder Co 850 516 Rev A firealarmresources co...

Отзывы: