Call Point Removal

How to remove the FC421CP-I

1 Remove the four fixing screws used to lock

the callpoint to the backbox.

2 Place the edge of a large flat bladed screw-

driver into the slot between the callpoint
cover and the backbox (see item

 

1 in Fig

 3).

3 Gently twist until the latches are disengaged.
4 Pull the cover away from the backbox.

Ordering Information

CPR Information

Fig. 3: FC421CP-I Removal
1

  – Screwdriver inserted into slot

Component

Ordering Numbers

FC421CP-I Outdoor
CP with isolator

514.800.806

Table 3: Ordering Information

 

1

0832

Tyco Fire & Security GmbH,

Victor von Bruns-Strasse 21,

8212 Neuhausen am Rheinfall,

Switzerland

15

DoP-2015-4170

EN 54-11 and EN 54-17

Manual callpoint with Short-Circuit Isolator 

for fire detection & fire alarm systems for 
buildings

Type A, Indoor

 FC421CP-I

Essential Characteristics
EN54-11

Nominal activation conditions / Sensitivity 

and Performance under fire conditions: Pass

EN54-17

Performance under fire conditions: Pass

EN54-11 and EN54-17

Operational reliability: Pass
Durability of operational reliability tempera-

ture resistance: Pass

Durability of operational reliability; vibration

resistance: Pass

Durability of operational reliability; humidity

resistance: Pass

Durability of operational reliability; corrosion

resistance: Pass

Durability of operational reliability; electrical

stability: Pass

FIRECLASS Fire detection system

 

FC421CP-I

Fixing instructions

 

Doc. version 4.0

1/4

FC421CP-I Outdoor Weatherproof Resettable 
Callpoint

Introduction

The FC421CP-I Weatherproof Addressable
Resettable Callpoint is an outdoor manual call-
point.
The callpoint is designed to monitor and signal
the condition of a switch contact that is operated 
by activating the resettable element.
The FC421CP-I is fitted onto a standard KAC
weatherproof backbox, which is supplied with
the callpoint. 
The

 

FC421CP-I has an integral short-circuit isola-

tor for monitoring the field wiring.
The FC421CP-I callpoint meets the requirements 
of EN54 Pt. 11 and EN54 Pt. 17.

Technical Specification

Table

 

1 shows the technical specification infor-

mation.

Fig. 1: FC421CP-I Outdoor Weatherproof Resettable Callpoint - Overall and Fixing Dimensions
1

  – Short Circuit Isolator Activation (Yellow) and Alarm Indicator LED (Red)
2

  – Test/Release Key Access
3

  – Earth Continuity Terminal (Internal)

97.5

93

73

45.5

76.53

83.8

04.5 FIXING HOLES
(3) PLACES

1

2

Parameter

Value

System Compatibility

Use only with FIRE-
CLASS Fire Alarm 
Controllers

Environment

Outdoor applications 

Operating
Temperature

-25 to +70

 

o

C

Storage Temperature

-30 to +70

 

o

C

Operating Humidity

Up to 95

 

%

  

non-condensing

Dimensions (HWD)

93 x 97.5 x 73

 mm

Weight

240

 

g

IP Rating

IP67

Table 1: Technical Specifications

 