31
(0=none, Yes=All)
Enter the number of the required zone and press
YES/ENTER
. The printer will produce a list of all points for which no
response was detected during the previous solo test of the selected zone(s), or were found to be faulty, together with any
available parameters.
The AUTOCALL TFX-500M/800M control panel display will respond with the following message:
Print initiated
TEST STARTED ”Zone label text” 4 13:55:06 30 JAN 90
Non Addressable Pnt.
Zone 4
POINT TESTED ”Zone label text”
Zone 04 A14
TEST FINISHED
All Zones 14:34:09 30 JAN 90
Non Addressable Pnt.
Zone 04 Point(s)
untested/failed
Address
Dev. Con. Id. LT. Av
Inst.
Cnfm. Status
Zone 4 A6 34
7.6
11.2
7.1mA
Norm
Norm
The first three entries above will be produced when (1) the solo test is initiated, (2) when each point is tested, and (3) when
the solo test is concluded, respectively performed. These entries will therefore already be on the printer before the print
option is selected. The entries in the summary table contain the following parameters:
Table 3--2 Printer message parameters and abbreviations.
Abbreviation
Parameter
Address
Zone, loop, and point number
Dev
Device type code number
Con
Current condition in mA
Id
Identity current in mA
LT. Av.
Long term average current in mA
Inst
Instantaneous point status
(Norm, Fault, Alarm, etc.)
Cnfm.
Confirmed point status
Print Event Log Backtrack
------ A printout of all (or part) of the Event Log may be obtained. Proceed as follows:
1. Select the “Print Event Log Backtrack”option from the Print Data menu. The display will respond with
the following message:
Enter No. events
2. Enter the number of events required for printing (for example, 20), and press
YES/ENTER
. The dis-
play will respond with the following message:
Print initiated
3. The AUTOCALL TFX-500M/800M control panel will print the (20) most recent events in the log, in
the form shown below:
EVENT LOG BACKTRACK
FIRE EVACUATE Factory 11:57:10:30 30 JAN 90
Ceiling Rose Zone 09 A 1
SYSTEM SILENCE System Zone 11:57:24:00 30 JAN 90
Non-Addressable Pnt. Zone 00 LB0 SO2
SYSTEM RESET All Zones 11:57:48:32 30JAN 90
Non Addressable Pnt. MP
firealarmresources.com
Содержание TFX-500M
Страница 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...
Страница 2: ...This page is blank firealarmresources com...
Страница 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...
Страница 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...
Страница 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...
Страница 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...
Страница 43: ...This page is blank firealarmresources com...