background image

31

(0=none, Yes=All)

Enter the number of the required zone and press

YES/ENTER

. The printer will produce a list of all points for which no

response was detected during the previous solo test of the selected zone(s), or were found to be faulty, together with any

available parameters.

The AUTOCALL TFX-500M/800M control panel display will respond with the following message:

Print initiated

TEST STARTED ”Zone label text” 4 13:55:06 30 JAN 90

Non Addressable Pnt.

Zone 4

POINT TESTED ”Zone label text”

Zone 04 A14

TEST FINISHED

All Zones 14:34:09 30 JAN 90

Non Addressable Pnt.

Zone 04 Point(s)

untested/failed

Address

Dev. Con. Id. LT. Av

Inst.

Cnfm. Status

Zone 4 A6 34

7.6

11.2

7.1mA

Norm

Norm

The first three entries above will be produced when (1) the solo test is initiated, (2) when each point is tested, and (3) when

the solo test is concluded, respectively performed. These entries will therefore already be on the printer before the print

option is selected. The entries in the summary table contain the following parameters:

Table 3--2 Printer message parameters and abbreviations.

Abbreviation

Parameter

Address

Zone, loop, and point number

Dev

Device type code number

Con

Current condition in mA

Id

Identity current in mA

LT. Av.

Long term average current in mA

Inst

Instantaneous point status

(Norm, Fault, Alarm, etc.)

Cnfm.

Confirmed point status

Print Event Log Backtrack

------ A printout of all (or part) of the Event Log may be obtained. Proceed as follows:

1. Select the “Print Event Log Backtrack”option from the Print Data menu. The display will respond with

the following message:

Enter No. events

2. Enter the number of events required for printing (for example, 20), and press

YES/ENTER

. The dis-

play will respond with the following message:

Print initiated

3. The AUTOCALL TFX-500M/800M control panel will print the (20) most recent events in the log, in

the form shown below:

EVENT LOG BACKTRACK
FIRE EVACUATE Factory 11:57:10:30 30 JAN 90
Ceiling Rose Zone 09 A 1
SYSTEM SILENCE System Zone 11:57:24:00 30 JAN 90
Non-Addressable Pnt. Zone 00 LB0 SO2
SYSTEM RESET All Zones 11:57:48:32 30JAN 90
Non Addressable Pnt. MP

firealarmresources.com

Содержание TFX-500M

Страница 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...

Страница 2: ...This page is blank firealarmresources com...

Страница 3: ...IONAL LTD COMPANY 835 Sharon Drive Westlake Ohio 44145 G i AUTOCALL TFX 500M and TFX 800M Fire Control System Operator s Manual Publication Number 850516 Issue 3 Revision A September 1997 firealarmres...

Страница 4: ...hority having jurisdiction For further information contact AUTOCALL TFX Products 835 Sharon Drive Westlake Ohio 44145 Telephone 440 871 9900 Facsimile 440 871 8320 WARNING This equipment generates and...

Страница 5: ...TFX 500M and TFX 800M AUTOCALL TFX 500 and TFX 800 CONSYSrProgramming Guide Publication Number 850463 Programming the TFX Fire Control System via a personal computer only authorized and trained person...

Страница 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...

Страница 7: ...ormal Operation 13 2 3 1 Access Levels 14 2 3 2 Initial Condition 14 2 3 3 Event Monitoring 14 2 4 Multiple Events 16 2 4 1 Event Priority 16 2 4 2 Alarm Resound Always Option 16 2 4 3 Bell Map Alarm...

Страница 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...

Страница 9: ...tting and operating the AUTOCALL TFX 500M and AUTOCALL TFX 800M fire alarm system requires the use of the special key Make sure you have one available Only authorized personnel may reset a fire contro...

Страница 10: ...NE TROUBLE LED yellow O KEYSWITCH F ALPHANUMERIC DISPLAY P PANEL SILENCE touch button G NO DELETE touch button Q ALARM SILENCE touch button H SCROLL UP touch button R SYSTEM RESET touch button I SCROL...

Страница 11: ...ARM LED red K POWER LED green B TROUBLE LED yellow L QUIT touch button C SUPERVISORY LED yellow M FAST ACCESS touch button D ZONE ALARM LED red N NUMERIC touch pad E ZONE TROUBLE LED yellow O KEYSWITC...

Страница 12: ...u do What happens Look at the AUTOCALL TFX 500M 800M control panels to see Alarms Listen for Alarm signals 1 Two red FIRE ALARM LEDs light 2 Red ZONE ALARM LED s flash 3 Buzzer sounds 4 Alarm bells ho...

Страница 13: ...panels to see SUPERVISORY lights and messages Listen for SUPERVISORY signals 1 Yellow SUPERVISORY LED light 2 Buzzer sounds a pulsing tone 3 Display gives SUPERVISORY message Read the display to deter...

Страница 14: ...ROUBLE lights and messages Listen for TROUBLE signals 1 Yellow TROUBLE LED light 2 Yellow ZONE TROUBLE LED s light 2 Buzzer sounds a pulsing tone 3 Display gives TROUBLE message Read the display to de...

Страница 15: ...TOR DISPLAY MODULE QUIT 23 JAN 94 22 17 02 1 Enter your passcode number or use Special Passcode 0911 and press YES ENTER The display will respond with the following message Do you want to accept event...

Страница 16: ...12 o clock position Allows access to touchpad functions Press ALARM SILENCE 1 Buzzer will change from constant to pulsing tone for alarm change from pulsing to off for trouble or supervisory alarm al...

Страница 17: ...p Zone 2 A48 001 FIRST SILENCE ALARMS RESET SYSTEM To reset the system 1 Accept events 2 Insert the key and turn the keyswitch to Enable 12 o clock position position 3 Press ALARM SILENCE to silence t...

Страница 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...

Страница 19: ...follows Figure 2 1 AUTOCALL TFX 500M 800M Keyswitch Positions Key FIRE TROUBLE SUPERVISORY POWER PANEL SILENCE ALARM SILENCE SYSTEM RESET DRILL ENABLE OFF LAMP TEST TURN CLOCKWISE TO 12 O CLOCK POSITI...

Страница 20: ...is pressed RESET Pressing RESET while the keyswitch is in the Enable position resets the system following the occurrence of an alarm or other event The system can only be reset after the signalling d...

Страница 21: ...LL TFX 500M 800M control panel to be operated from a remote location The front panel of the Remote Ops Dis panel is identical to that of the AUTOCALL TFX 500M 800M see Figure 1 2 or 1 3 It shows the s...

Страница 22: ...s 0001 to 9999 2 3 2 Initial Condition At initial power up the AUTOCALL TFX 500M 800M display shows the following message until the power up sequence is completed TFX 500 or TFX 800 initialising initi...

Страница 23: ...ed in the order of priority Event priority is as follows 1 FIRE EVACUATE 6 FAULTS ADDRESSABLE POINTS 2 FIRE ALERT 7 FAULTS CLEAR 3 WARNINGS 8 RESET SILENCE 4 FAULTS SYSTEM 9 PRINTER OFF LINE 5 SUPERVI...

Страница 24: ...the following will occur a Outstanding Events counter will be incremented b Signalling appliances will not be reactivated 3 If the bells horns strobes signalling appliances HAVE been silenced and the...

Страница 25: ...there are no other troubles or events the system will return to the normal or Standby mode The display will return to the normal date time display NOTE Alarms override trouble conditions Any trouble c...

Страница 26: ...el to remain in a Trouble condition The fire control system may not respond properly to a fire alarm condition Contact yourl Fire Protection Systems representative or Technical Services 835 Sharon Dri...

Страница 27: ...data Print Menu s Open VFP Available only at Cus tomer Manager access level and above Other options not shown are available at higher access levels Virtual Front Panel Menu Only available on ThornNet...

Страница 28: ...uence s Y Next Menu View Unrestored Events t Y Do you want to view log N or Events Display or No Events Found If there are unrestored events in the system the display will show the event s in the foll...

Страница 29: ...d in order of priority the highest priority first Press t to move forward through the log Press s to move backward through the log When either the beginning OR end of the log is reached an End of Log...

Страница 30: ...he zones may be viewed A 1 indicates that a zone or a point in the zone IS isolated a 0 indicates that it is not Thus for the example given below all or part of zones 1 and 16 are isolated Pressing QU...

Страница 31: ...ay be set Proceed as follows 1 Select the Set Time option The display will respond with the following message Enter time as HHMMSS In this display HH Hours MM Minutes SS Seconds The cursor will blink...

Страница 32: ...want to test system Do you want to sounders Do you want to isolate points t Y N or s Point solo test zone Zonal solo test Solo test Point solo test Solo test Sounder solo test Note During Solo Test S...

Страница 33: ...ontact monitor modules or detector monitor modules to be tested without raising an alarm Warning This function will disable the point s under test 1 Select the Solo Test Point option from the menu The...

Страница 34: ...ly 2 seconds every 30 seconds 4 Walk around the site to all indicating appliances Check for correct operation of the indicating appliances 5 When all the indicating appliances have been checked press...

Страница 35: ...mple Zone 1 has been isolated POINT ISOLATED 3rd Floor 12 15 00 23 Jan 90 Non Addressable Pnt Zone 1 Isolate Point 2 Way Data Circuits Only Individual devices may be isolated using their addresses Pro...

Страница 36: ...menu options sequence shown in Figure 3 8 will be displayed Figure 3 8 De Isolate menu options sequence s s t Y N or t Y N or Y Next Menu Do you want to de isolate pnts de isolate zone sensors only de...

Страница 37: ...ETE The display will return to that shown in Step 1 above 8 Once the correct loop has been chosen the display will respond with the following message Point no 0 none Yes all 9 Enter the address of the...

Страница 38: ...s in this menu allow the contents of the Event Log or the results of a Solo Test to be printed Figure 3 10 Print Data menu options sequence s s t Y N or t Y N or Y Do you want to print data Print poin...

Страница 39: ...in the summary table contain the following parameters Table 3 2 Printer message parameters and abbreviations Abbreviation Parameter Address Zone loop and point number Dev Device type code number Con...

Страница 40: ...ation point type number The MAXIMUM number of events that the log can hold is 150 Asking for more than this number will cause the AUTOCALL TFX 500M 800M control panel to display invalid try again 5 Th...

Страница 41: ...eceived attention Periodic System Checks The system can be configured to display a warning message accompanied by an audible alert when the system test is due This feature must be configured by an aut...

Страница 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...

Страница 43: ...This page is blank firealarmresources com...

Страница 44: ...rinted in the U S A Specifications and other information shown were current as of publication and are subject to change without notice 2001 Simplex Time Recorder Co 850 516 Rev A firealarmresources co...

Отзывы: