FUEL SUPPLY SYSTEM MANUAL with Touchscreen    •  SmartPump  •  page 5 of 22

®

OPERATION

1.  Connect a ground cable from the 

truck to the provided ground stud.

2. Unlock 

the 

fi ll box and connect a 

delivery hose to the hose coupling.

3.  Turn the Control Power switch to 

the ON position.

4.  Select the tank to fi ll using F1 or F2 

on the digital display.

5.  Press F4 on the digital display to 

open the fi ll valve for the selected 
tank. (Only one fi ll valve may be 
open at a time.)

6. The 

fi ll valve opens, and the pump 

starts.

7.  Open the valve on the truck.

8.  Start the delivery pump on the truck 

(if applicable).

9.  Fuel is delivered to the tank.

10. Delivery may be stopped at any 

time by pressing F5 on the digital 
display to close the fi ll valve and 
stop the pump.

11.  When the Tank Full level is reached, 

an alarm will be displayed and the 
tank fi ll valve will close. To reopen 
the valve for 30 seconds, press F3 
to override the high fuel level and 
top off the tank or drain the hose.

12.  When the Tank High level is 

reached, an alarm will be displayed; 
the fi ll valve will close and cannot 
be reopened until the fuel level falls 
below high level.

13. If any tank in the system reaches 

the Critical High level, an alarm will 
be displayed and no fi ll valves will 
be allowed to open.

14. During a fi lling operation, if any tank 

not selected for fi lling reaches Full, 
High or Leak, the selected tank’s 
fi ll valve will close. At this point the 
operator can reopen the selected 
fi ll valve if desired.

15.  Stop the delivery pump on the truck.

16.  Close the valve on the truck.

17.  Drain the delivery hose.

18. When the fi lling operation is com-

plete, press F5 to close the fi ll valve 
and stop the pump.

19.  Disconnect the delivery hose.

20. Turn the Control Power switch to 

the Off position.

21.  Close and lock the fi ll box.

22. Fuel delivery is complete; discon-

nect the ground cable from the 
trucker’s grounding stud.

TO DRAIN WITH
MOTOR-PUMP

1.  Start the pump by pressing F4 on the 

digital display. If the high fuel alarm 
is activated, press F3 on the digital 
display. Override is activated for 30 
seconds and can be reactivated until 
the critical high fuel level is reached.

2.  The pump will start. Operate the hand 

pump to prime the pump.

3.  Open the hand pump bypass valve.

4.  The pump will empty the spill basin. 

Note: Full basin will be emptied in 
about 20 seconds.

5. Stop the pump when the basin is 

empty by pressing F5 on the digital 
display.

Содержание SmartPump

Страница 1: ...SMARTPUMP MANUAL with Touchscreen January 2011...

Страница 2: ...lex Inc and or its subsidiaries Without written permission any copying transmitting to others and other use except that for which it is loaned is prohibited Contents DESCRIPTION 2 INSTALLATION 2 INITI...

Страница 3: ...k INSTALLATION 1 Anchor the Smart Pump to concrete pad using mounting holes provided in the base of the unit 2 Connect to an earth ground using the threaded ground stud in the lower left hand corner o...

Страница 4: ...wiring in solid conduits a Connectcontrolpowertoterminal block as shown on the drawings shipped with the equipment b Using 18 AWG or larger con nect the floatswitch assembly as shown Typical Transmitt...

Страница 5: ...c Place the customer supplied con trolpowercircuitbreakerintheOn position d Press F4 on the digital display The pump should start and run e Observe shaft rotation Rotation should be clockwise as view...

Страница 6: ...d analarmwillbedisplayed the fill valve will close and cannot be reopened until the fuel level falls below high level 13 If any tank in the system reaches the Critical High level an alarm will be disp...

Страница 7: ...ntainment of the tank Relay contacts to annunciate this alarm are provided PURGING THE PUMP Failure to Pump May Be Due to Air in the System It is necessary to purge the pump of air on initial start up...

Страница 8: ...itter The Receiver Indicator displays tank level on a 1 inch LCD display Level indicationcanbescaledinpercentlevel orgallonsforsquare rectangulartanks The Transmitter is installed in a 2 inch NPT or l...

Страница 9: ...d Transmitter Drawing A weatherproof conduit hub with 0 50NPT conduit fittings is provided for electrical connections Connection Usinga3conductorshieldedcable 20 AWG connect TC 25 Level Transmit ter t...

Страница 10: ...s Feet mA 15 0 1 25 4 947 15 5 1 29 4 978 16 0 1 33 5 010 16 5 1 38 5 041 17 0 1 42 5 073 17 5 1 46 5 104 18 0 1 50 5 136 18 5 1 54 5 167 19 0 1 58 5 199 19 5 1 63 5 230 20 0 1 67 5 262 20 5 1 71 5 29...

Страница 11: ...96 7 754 Inches Feet mA 60 0 5 00 7 786 60 5 5 04 7 818 61 0 5 08 7 849 61 5 5 13 7 881 62 0 5 17 7 912 62 5 5 21 7 944 63 0 5 25 7 975 63 5 5 29 8 007 64 0 5 33 8 038 64 5 5 38 8 070 65 0 5 42 8 102...

Страница 12: ...106 0 8 83 10 689 106 5 8 88 10 720 107 0 8 92 10 752 107 5 8 96 10 783 108 0 9 00 10 815 108 5 9 04 10 846 109 0 9 08 10 878 109 5 9 13 10 909 110 0 9 17 10 941 110 5 9 21 10 973 111 0 9 25 11 004 11...

Страница 13: ...0 5 12 54 13 497 151 0 12 58 13 528 151 5 12 63 13 560 152 0 12 67 13 591 152 5 12 71 13 623 153 0 12 75 13 654 153 5 12 79 13 686 154 0 12 83 13 717 154 5 12 88 13 749 155 0 12 92 13 781 155 5 12 96...

Страница 14: ...5 5 16 29 16 336 196 0 16 33 16 368 196 5 16 38 16 399 197 0 16 42 16 431 197 5 16 46 16 462 198 0 16 50 16 494 198 5 16 54 16 525 199 0 16 58 16 557 199 5 16 63 16 588 200 0 16 67 16 620 200 5 16 71...

Страница 15: ...233 0 19 42 18 702 233 5 19 46 18 734 234 0 19 50 18 765 234 5 19 54 18 797 235 0 19 58 18 829 235 5 19 63 18 860 236 0 19 67 18 892 236 5 19 71 18 923 237 0 19 75 18 955 237 5 19 79 18 986 238 0 19 8...

Страница 16: ...Close valve to selected tank To access system setup press and hold F1 F2 F3 2 System Setup F1 Access tank setup F2 Calibrate transducer factory set F3 Select PLC Modbus node F4SetPLCanalogcardtype fa...

Страница 17: ...Gallons Per Minute HFL High Fuel Level Relay HG Mercury HP Horsepower HZ Hertz I D Inside Diameter JB Junction Box Hz Hertz INHG Inches of Mercury L Lamp L E D Light Emitting Diode LAFD Los Angeles F...

Страница 18: ...I 1714 Torque lb in CU IN REV x PSI 2 Torque lb in HP X 63025 RPM Flow gpm CU IN REV x RPM 231 Head and Pressure Equivalents When converting pressure from feet of water to P S I the specific gravity o...

Страница 19: ...7 6 6 0 1 9 0 1 3 8 6 8 2 1 7 7 2 7 1 3 1800 11 5 1 3 11 1 1 10 7 1 13 7 13 3 1 12 9 1 10 9 3 10 2 5 426 1200 10 0 8 2 1 6 3 1 12 0 11 0 1 10 5 1 1800 15 0 1 12 2 1 9 5 3 18 0 1 17 0 1 16 0 3 428 1200...

Страница 20: ...6 1 8 1 1800 5 0 1 3 4 9 4 9 4 7 1 4 2 1 3 4 2 424 1200 8 8 8 7 1 8 5 1 8 2 2 7 8 3 1800 13 0 1 12 7 2 12 5 2 10 2 3 9 9 5 426 1200 12 5 1 12 0 1 11 8 2 1800 18 7 2 18 5 2 17 0 3 428 1200 24 9 2 24 5...

Страница 21: ...rate Starting Torque Sleeve Bearing NEMA Thermal Service Approx HP RPM Voltage Frame Prot Factor F L Amps 1 1800 115 208 230 56 Auto 1 15 13 4 6 8 6 7 11 2 1800 115 208 230 56H Auto 1 15 18 0 9 3 9 0...

Страница 22: ...3 5 1800 230 460 184T Auto 1 15 13 2 6 6 7 1 2 1800 230 460 213T Auto 1 15 20 0 10 0 10 1800 230 460 215T Auto 1 15 26 6 13 3 Totally Enclosed Fan Cooled Rigid Base Class B Insula tion Class F 182T 25...

Страница 23: ...39 No 5A 82 to 95 1 480 420 215 125 72 48 No 5B 82 to 95 850 600 490 400 315 235 178 141 No 6 82 to 95 72 000 21 500 7 800 2 150 590 225 110 Navy Spec 989 Max 3 300 1 100 600 360 190 100 66 50 2 Navy...

Отзывы: