FUEL SUPPLY SYSTEM MANUAL with Touchscreen • SmartPump • page 4 of 22
®
INITIAL START-UP TEST
PROCEDURES
1. The unit is operated with the control
panel outer door open to reveal op-
erator control panel. Do not access
the interior of the control panel with
the customer supplied control power
circuit breaker On.
2. Flip the customer supplied control
power circuit breaker to the On posi-
tion.
a. The Power Available indicator will
illuminate.
3. Check direction of rotation and opera-
tion of the pump and motor.
a. Place the customer supplied con-
trol power circuit breaker in the Off
position.
b. Remove shaft coupler guard from
the pump.
c. Place the customer supplied con-
trol power circuit breaker in the On
position.
d. Press F4 on the digital display.
The pump should start and run.
e. Observe shaft rotation. Rotation
should be clockwise as viewed
from above.
f. If rotation is incorrect:
1. Press the Pump Stop push-
button.
2. Ensure the customer supplied
control power circuit breaker is
Off.
3. Open the Control Panel inner
door to access the control
compartment.
4. Locate the overload relay,
labeled OLR. On either side
of the relay, reverse the black
and red wires: connect the red
wire to line one and the black
wire to line two.
Lethal high voltages may exist
within the control compartment.
The customer supplied control
power circuit breaker must be in
the Off position before opening
the compartment.
Rotating equipment. Pump/mo-
tor shafts and coupler rotates
at 3600 RPM. Observe guards.
5. Close the Control Panel in-
ner door and repeat steps C
through E.
g. Place the customer supplied con-
trol power circuit breaker to the Off
position. Reinstall the shaft guard.