FUEL SUPPLY SYSTEM MANUAL with Touchscreen    •  SmartPump  •  page 17 of 22

®

APPENDIX B  -   TECHNICAL DATA

 Conversion Factors

1HP = 33,000 ft. lbs. per minute
1HP = 42.4 btu per minute
1HP = 0.746 kwhr (kilowatt hours)

1 U.S. gallon= 231 cubic inches

Pipe Volume varies as the square of the diam-
eter; volume in gallons = 0.0034 D

 2

 L where:

  D=inside diameter of pipe in inches;
  L=length in inches

Velocity in feet per sec.= 0.408 

fl ow (gpm)

 

D

2

where: 
  D=inside diameter of pipe in inches

Atmospheric pressure at sea level = 14.7PSI
Atmospheric pressure decreases 
approximately 0.41PSI for each one thousand 
feet of elevation up to 23,000 feet.

Pressure (PSI) = feet head x 0.433 x specifi c 
gravity

Specifi c gravity of oil is approximately 0.85.

Thermal expansion of oil is approximately 
1 cubic inch per 1 gallon per 10°F rise in 
temperature.

 Hydraulic Formulas

Horsepower  =   GPM x PSI

 

1714

Torque (lb. in.) =  CU IN./REV. x PSI

 

2

Torque (lb. in.) =  HP X 63025

 

RPM

Flow (gpm) =  CU IN./REV x RPM

 231

 Head and Pressure 
Equivalents

When converting pressure from feet of water to 
P.S.I., the specifi c gravity of the liquid must be 
considered.

Here are some typical conversion fi gures:

  1 P.S.I.=2.30 feet of water 
 (specifi c gravity 1.0)

  1 P.S.I.=2.88 feet of oil 
 (specifi c gravity 0.8)

PRESSURE AND

CONVERSION TABLE

  Feet PSI  PSI
 Water 

Oil 

Water

 1 

.35 

.43

 2 

.70 

.87

 3 

1.05 

1.3

 4 

1.4 

1.73

 5 

1.75 

2.17

 10 

3.5 

4.33

 15 

5.2 

6.5

 20 

7.0 

8.66

 25 

8.7 

10.8

 30 

10.5 

13.0

 35 

12.2 

15.2

 40 

14.0 

17.3

 45 

15.7 

19.5

 50 

17.5 

21.7

 55 

19.2 

23.9

 60 

21.0 

26.0

 65 

22.7 

28.1

 70 

24.5 

30.5

 75 

26.2 

32.5

 80 

28.0 

34.6

 85 

29.7 

36.8

 90 

31.5 

39.0

SUPER X-L PUMP

 

 

 

 

 

 

Flow, GPM (LPM)

 PUMP 

DISPLACEMENT 

RPM 

100 PSI 

1000 PSI 

1500 PSI 

2000 PSI 

2500 PSI

 MODEL 

IN

3

 (CC/REV.) 

 

(6.9 Bar) 

(69 Bar) 

(103 Bar) 

(138 Bar) 

(172 Bar)

 

SUPER  .262 

1800 

1.99 1.86 1.79 1.73 1.66

 

XL-11 

(4.29) 

 (7.54) (7.05) (6.78) (6.56) (6.29)

 

SUPER  .942 

1800 

7.08 6.87 6.77 6.66 6.56

 

XL-39 

(15.44) 

 (26.83) (26.04) (25.66) (25.24) (24.86)

 

SUPER  1.47 1800 

11.10 10.81 10.70 10.60 10.40

 

XL-62 

(24.14) 

 (42.07) (40.97) (40.55) (40.17) (39.42)

 

SUPER  2.23 1800 

16.70 16.50 16.30

 

XL-90 

(36.5) 

 (63.29) (62.54) (61.78)

 

SUPER  3.35 1800 

25.30 24.90 24.60 24.40

 

XL-114 

(54.9) 

 (95.89) (94.37) (93.23) (92.48)

Содержание SmartPump

Страница 1: ...SMARTPUMP MANUAL with Touchscreen January 2011...

Страница 2: ...lex Inc and or its subsidiaries Without written permission any copying transmitting to others and other use except that for which it is loaned is prohibited Contents DESCRIPTION 2 INSTALLATION 2 INITI...

Страница 3: ...k INSTALLATION 1 Anchor the Smart Pump to concrete pad using mounting holes provided in the base of the unit 2 Connect to an earth ground using the threaded ground stud in the lower left hand corner o...

Страница 4: ...wiring in solid conduits a Connectcontrolpowertoterminal block as shown on the drawings shipped with the equipment b Using 18 AWG or larger con nect the floatswitch assembly as shown Typical Transmitt...

Страница 5: ...c Place the customer supplied con trolpowercircuitbreakerintheOn position d Press F4 on the digital display The pump should start and run e Observe shaft rotation Rotation should be clockwise as view...

Страница 6: ...d analarmwillbedisplayed the fill valve will close and cannot be reopened until the fuel level falls below high level 13 If any tank in the system reaches the Critical High level an alarm will be disp...

Страница 7: ...ntainment of the tank Relay contacts to annunciate this alarm are provided PURGING THE PUMP Failure to Pump May Be Due to Air in the System It is necessary to purge the pump of air on initial start up...

Страница 8: ...itter The Receiver Indicator displays tank level on a 1 inch LCD display Level indicationcanbescaledinpercentlevel orgallonsforsquare rectangulartanks The Transmitter is installed in a 2 inch NPT or l...

Страница 9: ...d Transmitter Drawing A weatherproof conduit hub with 0 50NPT conduit fittings is provided for electrical connections Connection Usinga3conductorshieldedcable 20 AWG connect TC 25 Level Transmit ter t...

Страница 10: ...s Feet mA 15 0 1 25 4 947 15 5 1 29 4 978 16 0 1 33 5 010 16 5 1 38 5 041 17 0 1 42 5 073 17 5 1 46 5 104 18 0 1 50 5 136 18 5 1 54 5 167 19 0 1 58 5 199 19 5 1 63 5 230 20 0 1 67 5 262 20 5 1 71 5 29...

Страница 11: ...96 7 754 Inches Feet mA 60 0 5 00 7 786 60 5 5 04 7 818 61 0 5 08 7 849 61 5 5 13 7 881 62 0 5 17 7 912 62 5 5 21 7 944 63 0 5 25 7 975 63 5 5 29 8 007 64 0 5 33 8 038 64 5 5 38 8 070 65 0 5 42 8 102...

Страница 12: ...106 0 8 83 10 689 106 5 8 88 10 720 107 0 8 92 10 752 107 5 8 96 10 783 108 0 9 00 10 815 108 5 9 04 10 846 109 0 9 08 10 878 109 5 9 13 10 909 110 0 9 17 10 941 110 5 9 21 10 973 111 0 9 25 11 004 11...

Страница 13: ...0 5 12 54 13 497 151 0 12 58 13 528 151 5 12 63 13 560 152 0 12 67 13 591 152 5 12 71 13 623 153 0 12 75 13 654 153 5 12 79 13 686 154 0 12 83 13 717 154 5 12 88 13 749 155 0 12 92 13 781 155 5 12 96...

Страница 14: ...5 5 16 29 16 336 196 0 16 33 16 368 196 5 16 38 16 399 197 0 16 42 16 431 197 5 16 46 16 462 198 0 16 50 16 494 198 5 16 54 16 525 199 0 16 58 16 557 199 5 16 63 16 588 200 0 16 67 16 620 200 5 16 71...

Страница 15: ...233 0 19 42 18 702 233 5 19 46 18 734 234 0 19 50 18 765 234 5 19 54 18 797 235 0 19 58 18 829 235 5 19 63 18 860 236 0 19 67 18 892 236 5 19 71 18 923 237 0 19 75 18 955 237 5 19 79 18 986 238 0 19 8...

Страница 16: ...Close valve to selected tank To access system setup press and hold F1 F2 F3 2 System Setup F1 Access tank setup F2 Calibrate transducer factory set F3 Select PLC Modbus node F4SetPLCanalogcardtype fa...

Страница 17: ...Gallons Per Minute HFL High Fuel Level Relay HG Mercury HP Horsepower HZ Hertz I D Inside Diameter JB Junction Box Hz Hertz INHG Inches of Mercury L Lamp L E D Light Emitting Diode LAFD Los Angeles F...

Страница 18: ...I 1714 Torque lb in CU IN REV x PSI 2 Torque lb in HP X 63025 RPM Flow gpm CU IN REV x RPM 231 Head and Pressure Equivalents When converting pressure from feet of water to P S I the specific gravity o...

Страница 19: ...7 6 6 0 1 9 0 1 3 8 6 8 2 1 7 7 2 7 1 3 1800 11 5 1 3 11 1 1 10 7 1 13 7 13 3 1 12 9 1 10 9 3 10 2 5 426 1200 10 0 8 2 1 6 3 1 12 0 11 0 1 10 5 1 1800 15 0 1 12 2 1 9 5 3 18 0 1 17 0 1 16 0 3 428 1200...

Страница 20: ...6 1 8 1 1800 5 0 1 3 4 9 4 9 4 7 1 4 2 1 3 4 2 424 1200 8 8 8 7 1 8 5 1 8 2 2 7 8 3 1800 13 0 1 12 7 2 12 5 2 10 2 3 9 9 5 426 1200 12 5 1 12 0 1 11 8 2 1800 18 7 2 18 5 2 17 0 3 428 1200 24 9 2 24 5...

Страница 21: ...rate Starting Torque Sleeve Bearing NEMA Thermal Service Approx HP RPM Voltage Frame Prot Factor F L Amps 1 1800 115 208 230 56 Auto 1 15 13 4 6 8 6 7 11 2 1800 115 208 230 56H Auto 1 15 18 0 9 3 9 0...

Страница 22: ...3 5 1800 230 460 184T Auto 1 15 13 2 6 6 7 1 2 1800 230 460 213T Auto 1 15 20 0 10 0 10 1800 230 460 215T Auto 1 15 26 6 13 3 Totally Enclosed Fan Cooled Rigid Base Class B Insula tion Class F 182T 25...

Страница 23: ...39 No 5A 82 to 95 1 480 420 215 125 72 48 No 5B 82 to 95 850 600 490 400 315 235 178 141 No 6 82 to 95 72 000 21 500 7 800 2 150 590 225 110 Navy Spec 989 Max 3 300 1 100 600 360 190 100 66 50 2 Navy...

Отзывы: