![Simplex LifeAlarm 4005 Series Скачать руководство пользователя страница 88](http://html1.mh-extra.com/html/simplex/lifealarm-4005-series/lifealarm-4005-series_programming-instructions-manual_1276528088.webp)
4-8
In the following example the activation of Monitor point 18-01 acts as a bypass
switch for the Third Floor Door and Signal circuits in both the East and West
wings (20-01 through 20-04).
1. Change the monitor point type of 18-01 to Utility (see the Edit Points,
Edit Point Type section of this publication) and label point 18-01 "Third
Floor Doors & Signals Bypass" (see the Edit Points, Edit Point Label
section of this publication).
2. Add point 18-01 to a user defined list (see the Lists, Add Points to a List
section of this publication) and label the user list "Third Floor Doors &
Signals Bypass" (see the Edit Points, Edit Point Label section of this
publication).
3. Change the point type of doors and signals to be bypassed to Relay and
Signal (see the Edit Points, Edit Point Type section of this publication).
4. Add all door and signal circuits to a user list and label the user list “Third
Floor Doors & Signals.”
5. Add signals to the Points OFF with Silence List 31-06.
6. Add doors to the Points OFF with Reset List 31-07
7. Change the custom label of the next available Digital Pseudo Point to “3
rd
Floor Doors & Signals Bypass Trouble” (see the Edit Points, Edit Point
Type section of this publication).
8. Change the Point Type of this Digital Pseudo Point to TROUBLE.
9. Add the following SMPL equations (see the To Start SMPL Programming
section of this publication):
Selective Bypass - Equation 1
Equation
Point Label
Point Type
,1$1<),5('(7 6\VWHP0RQ 0DQXDO(YDF
$1'1277%/
UG)OU'RRUV 6LJ%\SDVV
(QGRI,QSXW
+2/'2135,
UG)OU'RRUV 6LJ
(QGRI2XWSXW
Result: If fire is detected and the bypass switch is not activated, release doors and
sound signals.
Continued on next page
SMPL Language Applications,
Continued
Selective Bypass of
NAC/Relay Circuits
Technical Manuals Online! - http://www.tech-man.com
Содержание LifeAlarm 4005 Series
Страница 2: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 6: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 58: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 80: ...this is blank text Technical Manuals Online http www tech man com ...
Страница 129: ...6 9 SMPL Programming Continued SMPL Equations continued Technical Manuals Online http www tech man com ...
Страница 141: ...Technical Manuals Online http www tech man com ...
Страница 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...